NF DP060LM Instruction Manual page 257

Programmable ac power source
Table of Contents

Advertisement

Table 9-3 Actions When a Failure is Suspected (Continued)
Category
Symptom
Problem of
The Autocal
Autocal
function cannot
function
be turned on.
Problem of
Refer to "Instruction Manual (Remote Control)" in the attached CD-ROM.
remote
control
Problem of
The product
CONTROL
cannot be
I/O
controlled by the
CONTROL I/O.
Problem of
Files in the USB
USB
memory do not
memory
appear on the
screen.
Problem at
The current
driving an
waveform is
inductive
abnormal (e.g.,
load (e.g.,
asymmetrical or
transformer)
excessive) when
the transformer
is connected as
the load and the
AC voltage is
output.
DP060LM/DP120LM/DP180LM
Possible Cause
The output mode is
incorrect.
The waveform setting is
incorrect.
The mode is not the
Continuous mode.
The mode is not the
stand-by state of
Sequence mode.
In the stand-by state of
Sequence mode (step0)
and ACDC mode either
AC voltage or DC
voltage setting is not
0 V.
The AGC function is on. When the AGC function is on, the
The remote sensing
function is set to FB.
The external control is
disabled.
The Remote state is set
by the communication
interface.
USB eject operation was
performed.
One folder contains over
500 files.
The format is illegal.
The output offset
voltage (DC component)
caused the load
transformer core to
reach the magnetic
saturation.
9.2 When a Failure is Suspected
Necessary Actions
The Autocal function can be set to
on in the AC-INT, AC-VCA,
AC-SYNC, DC-INT, and
DC-VCA modes. However, for
the AC mode, it can be set to on
only when the waveform is a sine
wave. It is turned off when the
Sequence or Simulation function
is selected. However it can be set
to ON in the AC-INT, ACDC-INT
and DC-INT modes and when the
waveform is a sine wave or DC in
case the stand-by state of
Sequence mode (step0). In the
ACDC mode it cannot be set to
ON unless either AC voltage or
DC voltage setting is 0 V.
4.13
Autocal function cannot be used.
Turn the AGC function off.
4.12
Set the remote sensing function to
ON or OFF. 4.11
Enable the external control.
4.18
The external control is disabled in
the Remote state.
Perform the USB eject operation
(4.9) again just in case, and
remove the USB memory.
Reconnect the USB memory and
make sure the file names are
displayed.
Reduce the number of files in a
folder to 500 or less.
Use a FAT32-formatted USB
memory.
In the AC mode, the control
function works to eliminate the
offset voltage (DC component).
When the product is used in the
ACDC mode, switch it to the AC
mode. 3.4.2
If it does not bring much
improvement, adjust the DC
offset. 4.14
239