2. Preparation before Use
Single-phase
output terminal
Polyphase
output terminal
Connection procedure
The connection procedure of the single-phase output terminal follows the description in 2.5.1, and
that of the polyphase output terminal follows 2.5.2.
CAUTION
In the single-phase two-wire (1P2W) output, do not connect anything to the polyphase output
terminal.
In the single-phase three-wire (1P3W) output and the three-phase four-wire (3P4W) output, do
not connect anything to the single-phase output terminal.
In the single-phase three-wire (1P3W) output, do not connect anything to the L3 terminal.
2.5.1
Single-phase output
Connection procedure
1. Remove the resin-molded cover of power input and output panel in case DP060LM / DP120LM or
that of output panel in case DP180LM.
Also remove the single-phase output terminal cover in case DP120LM.
2. Connect the single-phase output terminal to the load with a cable. Be sure to tighten the screws
firmly. If you want to ground the output terminal at one point only, ground the Lo terminal. The Hi
terminal should not be grounded. If the load has a ground terminal, connect it to the chassis
terminal of the output terminal of this product.
CAUTION
The output terminal that can be grounded is the Lo terminals. Do not ground the Hi terminal.
3. Attach the single-phase output terminal cover with the bent part of the cover facing back side in
case DP120LM.
4. Attach the resin-molded cover of power input and output panel in DP060LM / DP120LM or that of
output panel in DP180LM so that the cables pass through the cutout.
18
Table 2-6 Screw Size of Output Terminal
DP060LM
M6 screw
M6 screw
DP120LM
M8 upset bolt
M6 screw
PROGRAMMABLE AC POWER SOURCE
DP180LM
M10 upset bolt
M6 screw