About arrangement
Stacking arrangement
Do not place the product on its side, back or top.
Do not stack the product on top of the other, or place it in front or back of the other
(arrangement which makes the cabinet placed behind inhale the exhaust heat of the other).
Other installation location conditions
Use the product indoors, at altitude up to 2000 m.
Use the product where the temperature is 0 to +50 degrees Celsius, and the humidity is 5 to
85 %RH (the absolute humidity should be 1 to 25 g/m
some specifications, the temperature range limit is more strict.
Do not install the product in the following places:
Place exposed to inflammable gas
This may pose a risk of explosion. Never install and use the product in such a place.
Outdoors, place exposed to direct sunlight, or place near fire or heat source
This may reduce the performance, or cause failure.
Place exposed to briny air
This may cause salt damage.
Place exposed to corrosive gas or water, or humid place
This may cause corrode or failure.
Place near electromagnetic field source, high-voltage equipment, or power line
This may cause malfunction.
Place of frequent vibration
This may cause malfunction or failure.
Dusty place
This may cause failure. Especially do not install the product in a place with conductive
dust.
Electromagnetic emissions from this product may interfere with reception of radio and
television broadcasts. Unless the user takes special measures to reduce electromagnetic
emissions, using this product in a residential area must be avoided.
DP060LM/DP120LM/DP180LM
・The center of gravity becomes high, which poses a risk of falling down.
・The product does not have a structure for supporting a heavy load.
Figure 2-3 Prohibited arrangement method
2.2 About Installation Environment
Tandem arrangement
・The product placed behind another will be overheated
by exhaust heat, which reduces the product's lifetime.