2.2
About Installation Environment
To use safely and maintain the reliability, take the followings into consideration:
Install the product where the exhaust heat will not damage surroundings.
This product performs forced air cooling using a fan. Keep the front and rear, on which the air
inlet and outlet are located, away from the wall at least 50 cm to secure air circulation.
This product exhausts the heat from the air outlet on the rear. Do not place heat-sensitive
objects around the outlet.
If you install the product in a closed narrow room, air conditioning equipment is required. The
heat value of DP series is shown in Table 2-2. The heat value of DP series Type R is shown in
Table 2-3.
Model
DP015S
DP030S
DP045S
DP060S
Single-phase
DP075S
DP090S
DP105S
DP120S
DP030D
DP060D
Single-phase
three-wire
DP090D
DP120D
DP045T
Three-phase
DP090T
DP045M
Multi-phase
DP090M
Note: Estimate at power input single-phase 200 V or three-phase three-wire 200 V or
three-phase four-wire 380 V (phase voltage 220 V), rated output.
DP Series/DP Series Type R
Table 2-2 Heat Value of DP series
Rated output
1.5 kVA
3 kVA
4.5 kVA
6 kVA
7.5 kVA
9 kVA
10.5 kVA
12 kVA
3 kVA
6 kVA
9 kVA
12 kVA
4.5 kVA
9 kVA
4.5 kVA
9 kVA
2.2 About Installation Environment
Heat value
0.5 kW
430 kcal/h
0.9 kW
780 kcal/h
1.4 kW
1210 kcal/h
1.8 kW
1550 kcal/h
2.3 kW
1980 kcal/h
2.7 kW
2320 kcal/h
3.2 kW
2760 kcal/h
3.6 kW
3100 kcal/h
0.9 kW
780 kcal/h
1.8 kW
1550 kcal/h
2.7 kW
2320 kcal/h
3.6 kW
3100 kcal/h
1.4 kW
1210 kcal/h
2.7 kW
2320 kcal/h
1.4 kW
1210 kcal/h
2.7 kW
2320 kcal/h
11