M800VS/M80V Series Connection and Setup Manual
15 Cable
15.3 Cable Relating to Drive Unit
15.3.9 J395 Cable
Max. cable length: 10 m
Application: Optical communication cable
for wiring between drive units (outside panel)
for wiring between NC-drive units
Use when wiring outside of the panel with a cable of 10 m or less.
OPT
OPT
1
2
[OPT]
Connector: LGP-Z0007PK
Manufacturer: HONDA TSUSHIN KOGYO
Cable
2-core cable (section with reinforced sheath)
2-core cable (section without reinforced sheath)
Note
(1) Binding the cables too tightly with tie-wraps could result in an increased loss or a disconnection. Use a cushioning mate-
rial such as a sponge or rubber when bundling the cables and fix so that the cables do not move. (Clamp material for ref-
erence: KITAGAWA INDUSTRIES CKN-13SP)
(2) Never bundle the cables with vinyl tape. The plasticizing material in the vinyl tape could cause the POF cable to break.
(3) Loop the excessive cable with twice or more than the minimum bending radius.
IB-1501613-A
OPT
OPT
1
2
Wire material: PFDU-CL1002-22E60VT
Manufacturer: TORAY
Minimum bending radius: R
362
50 mm
30 mm