M800VS/M80V Series Connection and Setup Manual
7 Connection of Control Unit
7.6 Connecting with Drive Unit
7.6.1.2 Drive Unit Arrangement
Arrange the drive units in the following procedure.
(1) Install a power supply unit.
(2) Arrange drive units in order of the nominal current from largest from the right.
(3) In the arrangement, the clearance between the units is 1 mm.
(4) Arrange the drive units with the DC connection length from the power supply unit being 1500 mm or less.
For the arrangement of 1500 mm or more, multiple power supply units are required.
(5) Arrange large capacity drive units at the left of the power supply unit with the clearance between the drive units being 1
mm.
Use the dedicated
connection bar.
POINT
(1) Arrange large capacity drive units at the left of the power supply unit with the clearance between the drive units
being 1 mm.
(2) Power supply units equivalent to the number of large capacity drive units are required.
(3) MDS-E-SP-400/640, MDS-EH-SP-200/320/480/600, and MDS-EH-V1-200 are the large capacity drive units.
1mm
Arrange drive units in order of nominal current from largest.
1mm
1mm
1mm
1500mm or less
Large
Small
229