M800VS/M80V Series Connection and Setup Manual
22 Setting the Position Detection System
22.1 Adjusting the Absolute Position Detection System

22.1.5 Dog-type

Preparations
(1)
Set the parameters on the absolute position parameter
screen.
Turn the power OFF and ON.
(2)
(Only when "#2049 type" is specified again.)
The following are the operations on the absolute position setting screen. ([Mainte] - [To Abs pos])
Select an axis to set the absolute position.
(3)
There are two methods to select an axis.
 Select the menu [Axis select], enter the axis name
in the input area then press [INPUT]. (For the axis
name, input the name set to the parameter "#1022
axname2" (2nd axis name).)
 Press the menu [Prev axis] and [Next axis] to switch
the axis.
Execute the manual or automatic dog-type zero point
(4)
return.
The axis arrives at the zero point.
(5)
The zero point initial setting is now complete. After initializing all axes, turn the power OFF and ON.
Note
(1) If the dog-type reference position return is interrupted by resetting, the previous state ("Complete" or "Illegality") will dis-
play in the [State] column.
(2) With dog-type reference position return, reference position return can be executed again even if the [State] is "Complete".
IB-1501613-A
#2049 type (absolute position detection method): 3 (dog-
type)
The parameters such as approach speed and grid mask
amount also need to be adjusted.
State: [Zero-P. Rel.]
Machine position: Current machine position
State: [Complete]
Machine position: 0.000
456
Selected axis