4 General Specifications
4.9 Remote I/O Unit
[Outline of digital signal output circuit]
Use within the specification ranges shown below.
<Output circuit>
Source output
CJ36
Stabilized
power supply
IO24VA
24VDC(+)
IO24VB
0V
IO0VA
FG
IO0VB
Load
Y00
Y02
|
Y06
COMA-
Load
Y01
Y03
|
Y07
COMB-
<Output conditions>
Insulation method
Rated load voltage
Maximum output current
Output delay time
IB-1501613-A
Voltage
conversion
Control
circuit
Voltage
conversion
Optocoupler insulation
24 VDC
2 A per point
8 A or less for whole unit
400 μs