M800VS/M80V Series Connection and Setup Manual
4 General Specifications
4.8 Operation Panel I/O Unit
[Outline of digital signal input circuit]
Both 24 V common and 0 V common connections are allowed in the digital signal input circuit.
Follow the wiring diagram below for each type.
<Input circuit>
24V common
CJ37/CJ39
External contact
X200
5kΩ
Stabilized
power supply
X25F
24VDC(+)
0V
DICOM
FG
<Input conditions>
Set the input signal within the range as shown in the conditions below.
1
Input voltage at external contact ON
2
Input current at external contact ON
3
Input voltage at external contact OFF
4
Input current at external contact OFF
5
Input resistance
6
Tolerable chattering time (T1)
7
Input signal holding time (T2)
8
Input circuit operation delay time (T3 and T4)
9
Machine side contact capacity
(*1) Input signal holding time: The guide is 40 ms or more. The input signal is recognized only when its "ON" state is held lon-
ger than the ladder processing cycle time.
Connection to 24 V common input
T2
(E)
T1
+24V
GND
(I)
T3
(E): External signal, (I): Internal signal
Note
 Set the number of DI points that are simultaneously turned ON to less than half of the total points.
If there are many points that are turned ON at the same time, operation panel I/O unit may deteriorate due to heat.
0V common
External contact
Stabilized
power supply
Control
circuit
24VDC(+)
0V
FG
24 V common
20.2 V or more, 25.2 V or less
Connection to 0 V common input
(E)
T1
T1
+24V
GND
(I)
T4
T3
83
CJ37/CJ39
X200
5kΩ
X25F
Control
circuit
DICOM
6 V or less
3 mA or more
0.7 mA or less
5 kΩ
3 ms
40 ms or more (*1)
3 ms to 16 ms
30 V or more, 16 mA or more
T2
T1
T4
0 V common
18 V or more, 25.2 V or less
3.8 V or less
IB-1501613-A