M800VS/M80V Series Connection and Setup Manual
7 Connection of Control Unit
7.12 Connecting I/O Device via Function Expansion Unit
(5) Insert the CC-Link cable into the connector of CC-Link unit.
Control unit
Note
 Connector of CC-Link unit is two-step structure. It is not different even if attach the cable to whichever.
(6) Insert the terminator to the connector of CC-Link unit as in the figure.
In the final station, the terminator connector is required.
Terminator
connector
Countermeasures for CC-Link dedicated cable noise
When the CC-Link expansion unit is being used, expose the cable by removing a part of the cable sheath and make sure to
use the shield clamp for the exogenous noise countermeasure.
Refer to "4.4 Shield connection to ground" of "CC-Link cable wiring manual" (published by CC-Link partner association) for
shield wire grounding for CC-Link dedicated cable.
[Related items]
Shield clamp fitting: "40.6.1 Shield Clamp Fitting"
IB-1501613-A
CC-link cable
CC-Link dedicated cable
Shield
244
CC-Link
expansion unit
Connector of
CC-link unit