Mitsubishi Electric M800VS Series Connection And Set Up Manual page 146

Hide thumbs Also See for M800VS Series:
Table of Contents

Advertisement

M800VS/M80V Series Connection and Setup Manual
4 General Specifications
4.9 Remote I/O Unit
Note
 When using an inductive load such as a relay, always connect a diode (voltage resistance 100 V or more, twice or more the
load current) in parallel to the load.
Source output
Inductive load
Y
Diode
 When the rush current exceeds the maximum output current indicated previously, always connect a protective resistor seri-
ally to the load to suppress rush currents. Make sure that the current is less than the maximum output current including the
momentary current.
Source output
Load Resistor
Y
 Always keep the total sum of output current of each Y00/Y02/Y04/Y06 and Y01/Y03/Y05/Y07 less than 4A.
2A or less per point
Y00
Total 4A
Y02
or less
Y04
Y06
Total 8A or less
CAUTION
(1) When using an inductive load such as a relay, always connect a diode in parallel to the load to prevent a counter-
electromotive force.
(2) When the rush current exceeds the maximum output current, always connect a protective resistor serially to the
load to suppress rush currents.
24VDC
Control
circuit
24VDC
Control
circuit
Y01
Total 4A
Y03
or less
Y05
Y07
115