Nortel DMS-100 Series Replacement Procedures page 1032

Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

1-1000 XPM card replacement procedures (continued)
NTMX72
in an RSC-S (PCM-30) Model B RCO2
16
17
18
19
297-8021-547 Standard 14.02 May 2001
After replacing the faulty card, load the inactive RCO2 unit by typing
>LOADPM
UNIT
unit_no
and pressing the Enter key.
where
unit_no
is the number of the inactive RCO2 unit
If LOADPM
passed
failed
Test the inactive unit by typing
>TST UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the inactive RCO2 unit
If TST
passed
failed
Use the following information to determine where to proceed.
If you entered this procedure
from
alarm clearing procedures
other
Return the inactive RCO2 unit to service by typing
>RTS UNIT unit_no
and pressing the Enter key.
where
unit_no
is the number of the inactive RCO2 unit
If RTS
passed
(continued)
Do
step 17
step 24
Do
step 18
step 23
Do
step 23
step 19
Do
step 20