1-1008 XPM card replacement procedures (continued)
NTMX72
in an SMA2
(end)
19
20
21
22
23
24
297-8021-547 Standard 14.02 May 2001
If you entered this procedure
from
other
Return the inactive SMA2 unit to service by typing
>RTS inactive
and pressing the Enter key.
If RTS
passed
failed
Remove the sign from the active SMA2 unit.
Go to the common returning a card procedure in this document.
Go to step 23.
Return to the procedure that directed you to this procedure. At the point
where a faulty card list was produced, identify the next faulty card on the list
and go to the appropriate card replacement procedure for that card in this
manual.
Obtain further assistance in replacing this card by contacting operating
company maintenance personnel.
You have successfully completed this procedure. Return to the maintenance
procedure that directed you to this card replacement procedure and continue
as directed.
Do
step 19
Do
step 20
step 23