„ CONTROL AND MONITORING ITEMS
NOTE: For detailed information, check the Interface Specification.
Item
ON/OFF Command
Operation Mode Setting
Temperature Setting
Airflow Mode Setting
Set Point Temperature Limit Setting
Thermostat Off setting
Indoor Unit
Control
(Individual /
Centrally Control (Filter Reset)
Batch)
Centrally Control (All Mode )
Centrally Control (Timer Mode)
Centrally Control (Set Temperature Mode)
Centrally Control (ON/OFF Mode)
Centrally Control (ON Mode)
Centrally Control (Operation Mode)
Filter Sign Reset
Antifreeze Setting
Indoor Unit
Control
Energy Save Mode Setting
(Individual)
Vertical/Horizontal Airflow Direction Louver
Setting
Time Setting
Indoor Unit
Control
(Batch)
Emergency STOP Setting
Outdoor Unit Low Noise
Outdoor
Unit Control
Outdoor Unit Capacity Save
(Individual)
ON/OFF Status
Operation Mode Setting Status
Temperature Setting Status
Airflow Mode Setting Status
Set Point Temperature Limit Status
Thermostat Off Setting Status
Centrally Control (Filter Reset) Status
Centrally Control (All Mode ) Status
Centrally Control (Timer Mode) Status
Centrally Control (Set Temperature) Status Remote controller set temp. prohibition status
Indoor Unit
Centrally Control (ON/OFF ) Status
Monitoring
Centrally Control (ON ) Status
(Individual)
Centrally Control (Operation ) Status
Antifreeze Setting Status
Energy Save Mode Setting Status
Filter Sign Reset Status
Room Temperature Status
Error Code Status
Vertical/Horizontal Airflow Direction Louver
Status
Indoor Unit Status
Function
Start / Stop operation
Cooling / Heating / Auto / Fan / Dry
Set room temperature
Set airflow
Set room temperature lower limit & room
temperature upper limit
Thermostat off
(Only one controller in VRF Network System can
do this)
Prohibition of filter sign reset of remote controller
Prohibition of all mode of remote controller
Prohibition of timer mode of remote controller
Prohibition of set temperature mode of remote
controller
Prohibition of ON/OFF mode of remote controller
Prohibition of ON mode of remote controller
Prohibition of operation mode of remote controller
Set filter sign reset command
Set antifreeze command
Set energy save command
Set Vertical/Horizontal airflow direction louver
Set time setting command
(The controllers those are connected in VRF
Network System are an object)
Set Emergency STOP command
Outdoor unit low noise level setting
Outdoor unit capacity save setting
ON / OFF status
Heating / Cooling / Auto / Fan / Dry mode status
Room set temperature status
Airflow mode status
Room set temperature limit status
Thermostat off set value status
Remote controller filter reset prohibition status
Remote controller all mode prohibition status
Remote controller timer mode prohibition status
Remote controller ON / OFF prohibition status
Remote controller ON prohibition status
Remote controller operation prohibition status
Antifreeze set status
Energy save mode set status
Filter sign reset status
Room temperature status
Error Code status can be monitored
Vertical/Horizontal Airflow Direction Louver
Status
Defrost / oil recovery / pumpdown can be
monitored
- (05 - 132) -