● Indoor units can be rotated according to the stoppage rate set for each group.
0%
20%
*The indoor unit operation stoppage rate can be selected from 10% to 30%.
Without control
z Outdoor unit capacity save function
The power consumption is reduced by limiting the upper limit of the outdoor unit capacity for
each refrigerant system.
This has a reducing effect especially in the summer, winter and other times when the heat load
is high.
In addition, because the upper limit capacity of the outdoor unit is limited directly, it is a control
which easily exhibits an energy saving effect compared to rotation control. However, because
the outdoor unit does not operate above the limited capacity, there may be a loss of comfort,
depending on the indoor heat load.
* The operation capacity upper limit rate [%] of the outdoor unit is specified for each refrigerant
system.
Maximum capacity
of outdoor unit
[%]
100
70
50
0
Group A
Group B
Group C
Group D
Time
[kW]
Indoor
heat load
0
[Time]
- (07-170) -
10%
30%
With control
Time