z Refrigerant circuit address setting
9) Pressing the SET BACK button, select a remote controller address (select the indoor unit
you want to operate).
*If the indoor unit you want to operate has already been selected, skip step 9)
10) Pressing the SET TIME < button or the SET TIME > button, display function number 02.
< : Down button
> : Up button
11) Pressing the SET TEMP. V button or the SET TEMP. Λ button, set up the refrigerant
circuit address data. (The setting range is from 00 to 99.)
12) Pressing the TIMER SET button, confirm the selected refrigerant circuit address data. (The
data will be transferred to the indoor unit.)
● When refrigerant circuit address data was not
set up on the indoor unit (-- is displayed.)
● Set up refrigerant circuit address data again
according to the procedure in step 11) above.
Remote controller address
Ex.) When remote controller address "01" is
selected
Function number
Refrigerant circuit address data
Ex.) When refrigerant circuit address data "18" is
set up
ERROR
When refrigerant circuit address data was
normally set up on the indoor unit
(Flashing display changes to illuminated display.)
- (07-27) -
GOOD