Vr-Ii Series - Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

2-1-1. VR-II series

„ SETTINGS LIST
LED105
Setting Mode
CODE No.
Pipe length
0
0
setting
Sequential start
1
0
shift
Cooling
1
1
capacity shift
Heating
1
2
capacity shift
1
3
Prohibited
1
4
Prohibited
1
5
Prohibited
*1: Do not set this for outdoor units with Slave setting.
LED104
Setting Function
CODE No.
0
0
Standard (40 to 65m)
0
1
Short (less than 40m)
0
2
Medium (65 to 90m)
0
3
Long 1 (90 to 120m)
0
4
Long 2 (120 to 150m)
0
0
Normal
0
1
21sec. Delay
0
2
42sec. Delay
0
3
63sec. Delay
0
0
Normal mode
0
1
Save energy mode 1
0
2
High power mode 1
0
3
High power mode 2
0
4
Prohibited
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
4
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
- (07-68) -
Outdoor unit
Factory
setting
Master Slave
l
Pipe length means the length
-
¡
between master outdoor unit
*1
and the nearest indoor unit.
The start-up timing of outdoor
l
unit (compressor) can be set
up so that it can delay several
seconds.
-
¡
This feature is useful when
*1
multiple number of outdoor units
are installed and turned on at
the same time
to limit the starting current.
l
-
¡
*1
l
-
¡
*1
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited
Remarks