9. SAFETY DEVICES
Model and type
AUXB04GBLH
AUXB04GALH
AUXB07GALH
Compact cassette
AUXB09GALH
AUXB12GALH
AUXB14GALH
AUXB18GALH
AUXB24GALH
AUXM018GLAH
AUXM024GLAH
AUXM030GLAH
AUXK018GLAH
Circular flow
AUXK024GLAH
AUXK030GLAH
cassette
AUXK034GLAH
AUXK036GLAH
AUXK045GLAH
AUXK054GLAH
AUXD18GALH
AUXD24GALH
AUXA18GALH
AUXA24GALH
Cassette
AUXA30GALH
AUXA34GALH
AUXA36GALH
AUXA45GALH
AUXA54GALH
ARXB07GALH
ARXB09GALH
Low static pressure
ARXB12GALH
duct / Concealed
ARXB14GALH
floor
ARXB18GALH
ARXK04GCLH
ARXK07GCLH
ARXK09GCLH
Mini duct
ARXK12GCLH
ARXK14GCLH
ARXK18GCLH
ARXK24GCLH
ARXD04GALH
ARXD07GALH
ARXD09GALH
Slim duct / Slim
ARXD12GALH
concealed floor
ARXD14GALH
ARXD18GALH
ARXD24GALH
*1) Fuse for fan motor.
*2) Including in the Drain Pump Unit (Optional parts)
Fan motor
Fuse
thermal
protector
Activate (at 125±10°C ):
Fan motor stop
Reset (at 120±10°C): Fan
motor restart
250V
Activate (at 140±20°C):
3.15A
Fan motor stop
Reset (at 110±20°C): Fan
motor restart
Activate (at 125±10°C ):
250V
Fan motor stop
Reset (at 120±10°C): Fan
3.15A
motor restart
Activate (at 110
250V
Fan motor stop
Reset (at 105+
3.15A
Fan motor restart
Activate (at 140 ± 5°C):
250V
Fan motor stop
3.15A
Activate (at 150 ± 5°C):
Fan motor stop
Activate (at 135±15°C ):
250V
Fan motor stop
Reset (at 115±15°C): Fan
3.15A
motor restart
Activate (at 135±15°C ):
250V
Fan motor stop
Reset (at 115±15°C): Fan
5A
motor restart
- (04-324) -
Terminal
Float
thermal fuse
switch
-
-
+15
°C):
-10
-
15
°C):
-10
-
*2)
-
-