Optional Parts Installation; Drain Pump Unit - Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

10. OPTIONAL PARTS INSTALLATION

10-1. DRAIN PUMP UNIT

„ MODEL : UTZ-PX1BBA
z Specifications
Height of drain up
Power source
Input Power (230V, 50/60Hz)
Current (230V, 50/60Hz)
Dimensions (H x W x D)
Weight
Connection pipe diameter
Direction of pipe connection
Angle of pipe connection
Control method
safety device
1 : Direction of pipe connection
*
z Application indoor units
Type
Low static pressure duct
/ concealed floor
z Mounting position
Strong and slide ceiling
Left
side
100 or more
Front view
3
597 * / 886 *
3
560 * / 850 *
Air
Top view
Unit
mm Maximum 1000
-
W
mA 114 / 92
mm 176 x 178 x 154
kg
-
1
-
*
2
-
*
-
-
ARXB07GALH, ARXB09GALH, ARXB12GALH,
ARXB14GALH, ARXB18GALH
Right
side
470 or more
Drain pump unit
4
167
4
178
- (10 - 64) -
Specifications
220-240V, 50/60Hz
12 / 10.8
2.5
VP25 (I.D.25mm, O.D.32mm)
360°
0° (Horizontal)-90° (Vertical)
Control board of indoor unit
Float switch, Thermal fuse
2 : Angle of pipe connection
*
Model name
Connected drain pipe (VP25)
(I.D. 25; O.D.32)
Front view
Note:
Leave the space required to service the unit.
Set a maintenance hole near the drain pump unit.
This product is specially designed for ceiling concealed
installation of the indoor unit.
It cannot be connected when it is installed on the floor.
*3 : ARXB07, 09
*4 : ARXB12, 14, 18
(Unit : mm)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents