„ LIMITED WIRING LENGTH
z For non-polar 2 wire
Indoor unit
A
B
Network convertor
A, B, C, D, E : Remote controller cable. (Refer to Chapter6. 4-4 for detail specifications.)
A ≤ 2 m and A + B + C + D + E ≤ 500 m
z For polar 3 wire
Indoor unit
A
B
X
SET TEMP.
START/STOP
Y
SET TEMP.
START/STOP
Network convertor
A, B, C, D, E, X, Y : Remote controller cable. (Refer to Chapter6. 4-4 for detail specifications.)
A ≤ 2 m, A + B + C + D + E ≤ 100 m and X + Y ≤ 100 m
C
D
E
C
D
E
- (05 - 123) -