Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 970

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

<<Outdoor unit + indoor unit + RB unit electricity charge apportionment>> → Connection of an
electricity meter to the outdoor unit, indoor unit and RB unit is necessary.
Whm
Whm
Whm
(11) Electricity apportionment for DX-Kit
● When electricity meter not connected
The following units can be linked to the DX-Kit, by using external output terminals.
[A]: External fan
[B]: Units linked to run/stop state external output
At electricity apportionment, the DX-Kit itself and units [A] and [B] mentioned above can be
handled. Set the electricity value at ON beforehand for the units [A] and [B] from the "Parameter
Setting" screen. The input value is included in the calculation as a constant value when the
external output terminal is ON.
DX-Kit
[B] External fan
[A] Run/stop state
External output linked units
- (07-189) -
Electricity meter is not connected to
some indoor units and RB units
Electricity meter is not connected to some
RB units