Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 738

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

„ WIRING RULES
● In the following cases, Signal Amplifier is required.
1) When the total length of the transmission line exceeded 500 m.
AB+BC+BD+DE+EF > 500 m (Fig. 1)
2) When the total number of units *1 is over 64.
● Transmission line length between each unit*1 : MAX 400 m.
● Total transmission line length: MAX 3600 m
AB+BC+BD+DE+EF+EG+GH ≤ 3600 m (Fig. 2)
Terminal
resistor
Outdoor unit
B
A
D
Indoor unit
When AB+BC+BD+DE+EF>500m
:Signal Amplifier is required.
*1: Refer detail Meaning of unit on 1-2 VRF NETWORK SYSTEM.
Fig. 1
Transmission line
System
C
Controller
E
F
Touch
Panel
Controller
- (06 - 47) -
Fig. 2
Terminal
resistor
Outdoor unit
A
Transmission line
B
D
Terminal resistor
E
G
NS 3
Signal Amplifier
Indoor unit
NS 1
Touch
C
Panel
Controller
NS 2
System
F
Controller
NS 4
H

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents