1-1-1. EXTERNAL INPUT

Setting to "Low noise mode", "Cooling priority/heating priority selection", "Outdoor unit
operation peak control", "Emergency/batch stop" and "Electricity meter pulse" are possible
from the outside.
„ WIRING METHOD AND SPECIFICATIONS
*A twisted pair cable (22AWG) should be used. Maximum length of cable is 150m.
* Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed
*For each input, pin No.1 is of positive polarity and pin No.2 is of ground level.
CN131
(Yellow)
1 2
P.C.B
Input1
connected unit
„ OPERATION BEHAVIOR
Connector
Input signal
OFF
CN131 (Yellow)
ON
CN132 (Green)
OFF
*1
ON
OFF
CN133 (White)
ON
OFF
CN134 (Red)
ON
CN135 (Orange)
No pulse
Pulse
*4
Slave unit can connect only input5 (CN135).
Note :
*1: The "external input priority mode" must be set by pressing push button on PC board of outdoor
unit.
*2: Batch stop or Emergency stop pattern can be selected by outdoor unit PC board push button.
*3: The emergency stop function mounted in the equipment does not guarantee the regulations of
each country. For this reason, sufficient checking is necessary regarding use.
Especially, since the fact that the equipment may not be emergency-stopped in the case of
breaking of the wiring to the external input terminals and communication line, communication
error due to noise, VRF external input circuit trouble, etc. must be considered, the provision of
double measures that add direct interruption of the power supply by switch, etc. is recommended
as a precaution.
*4: Pulse input to CN135 must be width 50ms or more, and must be interval 50ms or more.
CN132
CN133
(Green)
(White)
1 2
1 2
Input2
Input3
connected unit connected unit connected unit connected unit
Normal operation
Low noise mode operation
Cooling priority
Heating priority
Normal operation
Outdoor unit operation peak control
Normal operation
Batch stop or Emergency stop operation *2, *3
No information from electricity meter
Power usage information from electricity meter
- (08 - 04) -
CN134
CN135
(Red)
(Orange)
1 2
1 2
Input4
Input5
Status
Outdoor unit
Master
Slave