„ COMPLETION OF ADDRESS SETTING MODE
11) When the [Back] on the "Function Setting" screen is touched, the display returns to the
"Maintenance" screen.
Function Setting
Address
Function No.
Setting No.
Back
„ SETTING UP EACH INDOOR UNIT
Indoor unit
01
Wired remote
controller
(Touch panel)
Repeat the procedures in steps 1) through 11), and set up the indoor units
requiring address setting.
„ RESET THE POWER AFTER SETTING UP ADDRESS OF ALL
INDOOR UNITS
Important
¾ If the reset is not performed, address can not be read in normally.
¾ After all the addresses have been set, the circuit breaker needs to be switched off
for at least 2 minutes.
After the 2 minutes has passed, power can be restored.
¾ The set address is stored in the PCB and will remain in memory even when the
power is turned off.
However setting address is effective after power reset.
Record the address set in the indoor unit on a label, etc., and affix the label to the
unit so it can be used for after-sales service operations.
[002–01]
[30]
[01]
Setting
Indoor unit
Indoor unit
00
0
01
01
0
01
02
0
- (07-124) -
Indoor unit
Indoor unit
01
13
0
01
Wired remote
Wired remote
controller
controller
(Touch panel)
(Touch panel)
Indoor unit
14
0
01
15
0