„ VRF TERMINAL RESISTER SETTING (SET 2-1)
When there is no outdoor unit or signal amplifier in the VRF network segment to which the converter is connected,
set to "ON."
ON: Terminal resistance enable
OFF: Terminal resistance invalid (Default)
„ TEST RUN SETTING (SET 2-3)
Test run start and reset can be set.
ON: Test run starts
OFF: Test run resets (Default)
„ SCAN SETTING (SET 2-4)
SCAN start and reset can be set.
ON: SCAN starts
OFF: SCAN resets (Default)
„ Programming Button (Prog Button)
Used for communication with the ETS of tool for KNX.
ETS is a software, which runs on Windows
Push to toggle between the modes.
Runtime mode (Default)
[PROG LED off]
„ CONFIGURATION AND SETUP
This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS.
For how to configure the settings from the ETS, refer to the Interface Specification.