z MODEL: UTY-DTG 
No.
Item
Language setting
Indoor unit registration
1
Installation
Functions setting
Display switching
Display units
Monitor contents (icon display)
2
Monitor
Monitor contents (list display)
Error list
Special state
Control units
3
Control
Control contents
Detailed control contents
Date and time
Panel cleaning and correction
Group
Background light and beep
sound
Password
4
Setting
Schedule timer
Temperature range
Network
Low noise operation
Time zone
Electricity charge
apportionment
User setting (Admin:5,
User:100)
Automatic logout
Remote
Permission
5
connection
Unit setting
Mail setting
6
Others
External input/output
● When Start/Stop, operation mode setting, room temp. setting, fan speed setting, air flow direction setting, swing
setting, economy mode, and anti freeze setting are changed frequently by using the central controller like System
Controller, Touch Panel Controller, etc. or from Building Management System (BMS) via BACnet
Network Convertor, the number of operations for each indoor unit must not exceed 7,500 times/year.
If the number of setting change exceeds the above specified number, the rewriting count limit of the non-volatile
memory (memory built into the air conditioner and used for recording settings) will be exceeded, and may cause
breakdown.
*1 : Product specifications are subject to change without notice.
Description
Design considering multi-language correspondence. *1
Indoor unit registration. Max. 400 units.
(Set data can be written to and read from USB flash drive)
Temperature set point limitation, external input, central operation
on/off setting.
Icon display, list display
ALL, group, individual (remote control group)
Group name, operation, operation mode, set temperature, time,
errors, timer setting, filter sign
Group name, operation, operation mode, set temperature, airflow,
air direction, special operation, anti-freeze, time, errors, timer
setting, filter sign
Group name, remote control group name, address, error code
Display during special operation
ALL, group, individual (remote control group)
Operation, operation mode, set temperature, airflow,
RC Prohibition, filter sign reset
Air direction, energy saving, anti-freeze, test run
Time display switching, year/month/day display switching, system
clock setting, summer time
Select display area for panel cleaning.
User can select black screen on display.
Stages: Max. 3 stages Settable up to 400 groups.
(Set data can be written to and read from USB flash drive)
Backlighting off time and brightness setting, BEEP sound
operation setting
Management level: 3 kinds
Max. 30 items settable
Celsius/Fahrenheit switching, cooling, heating, and AUTO each
settable.
function of Email notification for malfunction, or electricity charge
apportionment option is used via LAN
"Low noise operation" is set to all the outdoor units registered by
this controller.
Set the time zone of the area where this unit is used
Start/stop of ECA, importing/exporting of ECA setting, and
exporting ECA data.
Register the user or administrator who is permitted to use remote
connection operation.
Can be set Automatic logout.
Can be select the functions.
Can be select the units.
When an error is generated at the touch panel controller or a
registered outdoor unit or indoor unit, an Email can be sent to a
pre-registered address.
Input: Batch operation/stop, emergency stop, electricity meter
Output: Operation monitoring, error
- (05 - 41) -