Example Of Refrigerant System - Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

1-1-1. EXAMPLE OF REFRIGERANT SYSTEM

z Example 1 (OK)
Outdoor unit
Model
Outdoor unit
AJ  072L
Indoor unit 1
AUXD24
Indoor unit 2
AUXD24
z Example 2 (OK)
Outdoor unit
Model
Outdoor unit
AJ  072L
Indoor unit 1
AUXA30
Indoor unit 2
AUXA30
Indoor unit 3
AUXB24
z Example 3 (Prohibited)
Outdoor unit
Model
Outdoor unit
AJ  072L
Indoor unit 1
AUXA54
Indoor unit 2
AUXA54
Indoor unit 3 AUXK036
Indoor unit 1
Indoor unit 2
Total
Connectable indoor
Capacity
capacity
(kW)
(kW)
22.4
22.4
9.0
9.0
18.0
Indoor unit 2
Indoor unit 1
Connectable indoor
Total
Capacity
capacity
(kW)
(kW)
22.4
22.4
9.0
9.0
25.1
7.1
Indoor unit 1
Indoor unit 2
Connectable indoor
Total
Capacity
capacity
(kW)
(kW)
22.4
22.4
14.0
14.0
39.2
11.2
- (06 - 02) -
Capacity ratio
80%
unit capacity
Min.
Max.
 50%
 150%
11.2
33.6
Indoor unit 3
unit capacity
Min.
Max.
 50%
 150%
11.2
33.6
Indoor unit 3
unit capacity
Min.
Max.
 50%
 150%
11.2
33.6
Judgement
 ≤
≤ 
11.2 < 18.0 < 33.6 → OK
Capacity ratio
112%
Judgement
 ≤
≤ 
11.2 < 25.1 < 33.6 → OK
Capacity ratio
175%
Judgement
 ≤
33.6 < 39.2 → Prohibited