Wiring System - Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

1-5. WIRING SYSTEM

● Wiring configulation of the control system is made of power source wiring, transmission wiring, and remote controller wiring.
● Total wiring length (total length of transmission line) can be extended up to 3,600 m (by using signal amplifiers).
To outdoor units
(Remote / Monitoring side)
Internet
Touch Panel Controller
One Touch panel controller can control
up to 400 groups / 400 indoor units.
Central Remote Controller
Maximum 100 indoor units can be controlled
®
BACnet
Gateway
®
BACnet
UTY-ABGXZ1
®
BACnet
BACnet
®
Operator
Workstation (B-OWS)
Modbus® Convertor UTY-VMGX
Modbus®
Network Convertor UTY-VLGX
®
L
W
ON
ORKS
Transmission Line
line is non-polar 2-conductor.
Signal Amplifier
UTY-VSGXZ1
Web Monitoring Tool
Trouble free operation at all times
by remote monitoring system.
Web Monitoring Tool
UTY-AMGXZ1
Internet
(VRF network system side)
(Monitoring side)
(Monitoring side)
(Monitoring side)
Combination of individual remote controller
Wired, simple and wireless remote controllers can be used jointly.
System Controller UTY-APGXZ1 or System Controller Lite UTY-ALGXZ1
• Maximum 1,600 indoor units can be controlled. *1
• Air conditioning control
• Operation monitoring
• Status monitoring system
• Electricity charge calculation *2
USB Adaptor
NW1
NW2
*3
NW3
*3
NW4
*3
Group Remote Controller
Maximum 8 remote controller groups can be
controlled
Network Convertor
UTY-VGGXZ1
USB
Adaptor
Remote controller line (3-wire)
Maximum 16 units can be controlled
Modbus
®
network
System without Remote Controller
Together with Touch panel controller, it is
possible to build non remote controller system.
®
L
W
ON
ORKS
network
2 Remote Controllers
Indoor unit can be controlled
from both remote controllers.
USB
Adaptor
Service Tool
UTY-ASGXZ1
USB Adaptor
Service Tool
Extensive monitoring and analysis
functions for installation and maintenance.
Internet
or
Public Telephone Line
Remote controller line (2-wire)
Maximum 16 units can be controlled
IR Receiver Unit
Duct type indoor unit
can be controlled
with wireless remote
controller.
External Switch Controller
Indoor units can be controlled by combining
with Card-key switch such as hotel room.
Network Convertor
UTY-VTGX or UTY-
VTGXV or UTY-VGGXZ1
Multi system
Indoor unit
Touch Panel
(Cassette)
Controller
Central Remote
Indoor unit
Controller
(Duct)
RB unit
Group Remote
(Single)
Controller
Wired Remote
RB unit
(Multi)
Controller
- (05 - 14) -
Max. Transmission
line length
3,600 m
(Remote / Monitoring side) *2
Case of UTY-ALGXZ1
*1: Maximum 400 indoor units can be controlled.
*2: Option is necessary.
*3: Can not be used.
Internet
Smart device
Wireless LAN Adapter
Remotely manage an Air Conditioning
system using all sort of mobile devices
such as Smartphones, and tablets.
Card key
Network Convertor
UTY-VTGX or UTY-
VTGXV or UTY-VGGXZ1
Single system
Transmission line
Simple Remote
Controller
Module link
Remote controller
Simple Remote
line (3-line)
Controller
Remote controller
Simple Remote
line (2-line)
Controller
USB cable
Wireless Remote
Signal line
Controller
(single system)
External Switch
Controller
IR Receiver unit

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents