Decide the mounting position with the customer as follows:
(1) Install EV kit level on strong wall, floor, ceiling which is not subject to vibration.
(2) Install EV kit where the connection pipe can be easily installed.
(3) Install EV kit where vibration and noise are not amplified.
(4) Take servicing, etc. into consideration and leave the space as follows.
300mm or more
INSTALLATION METHOD
The installation direction can be selected either horizontal (Pattern A) or vertical (Pattern B),
but keep the inclination within 5º.
Incorrect installation direction or angle may cause improper operation.
z Suspended installation
(1) Remove the 2 screws and replace them with the hanger.
(2) Use the hanger bolts to fasten the hanger.
Hanger
Screw
Pattern A
Level
Wire
Horizontal installation
- (06 - 38) -
CAUTION
Vertical installation
Pattern B
Level
Wire
M10 hanger bolt
(Locally purchased)
Special nut A
Special nut B