Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 1012

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

z Apply voltage contact
When a power supply must be provided at the input device, connect to CN11 and CN12.
*2
DC power
supply 24V
*4
*4
Connected unit
*2 : Make the power supply 24V. Select a power supply capacity with an ample surplus for the
connected load.
*3 : Do not impress a voltage exceeding 24V across pin 1, 3.
*4 : The allowable current is DC5mA or less. (Recommended DC5mA)
Provide a load resistance such that the current becomes DC5mA or less.
* A twisted pair cable(22AWG) should be used. Maximum length of cable is 25m.
„ INPUT SIGNAL TYPE
The input signal type can be selected.
Edge
Pulse
PCB
3
1
3
1
CN11
CN12
(White)
(Green)
● Press the [
cursor to the "Operation" menu.
[Emergency Stop] button : Enables
Emergency stop by external input.
[All On/All Off] button : Enables batch
operation On/Off by external input.
[Not Used] button : Does not receive
external input signals.
● Press the [
cursor to the "Input Method" menu.
[Edge] button : Detects the signal rise
and fall.
[Pulse] button : Detects the signal level.
● When the [
is complete.
- (08 - 36) -
] button and move the
] button and move the
] button is pressed, setting

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents