Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 787

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

„ SETTING EXAMPLE
● Outdoor unit setting
SetA: Refrigerant circuit address
(Rotary SW REF AD x10, x1)
SetB: Outdoor unit address
SetA
SetB
(DIP SW SET3-1, 3-2)
00
0
SetC: Number of slave unit
SetC
SetL
(DIP SW SET3-3, 3-4)
2
3
<Master unit only>
SetL: Number of outdoor units
installed
(DIP SW SET5-1, 5-2)
● Touch panel controller setting
SetG: Controller address (Max.16)
● Network convertor setting
SetH: Convertor address
(for Group remote controller:Max.16)
Refrigerant circuit address
(for Single split AC:Max.100)
● Central remote controller setting
SetN: Controller address (Max.16)
● Group remote controller setting
SetI: Group remote controller address
(Max.4)
● Signal amplifier setting
SetK: Signal amplifier address
¾
Instructions for setting up the address
1. The refrigerant circuit address of the indoor units, outdoor units and RB units can be set to arbitrary numbers in the
range of 0 to 99.
2. The Indoor unit address and RB unit address can be set to arbitrary numbers in the range of 0 to 63.
3. In case of 3-wire type of R.C., set the remote controller address in the order of 0,1,2, . . . ,15.(Blank is not allowed)
4. In case of 2-wire type of R.C.(Automatic address setting), set the remote controller address in the 0.
5. Touch panel controller address can be set to arbitrary numbers in the range of 0 to 15.
6 : The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote controller
®
, Modbus
convertor and Network convertor for L
7. Keep Address No. of Touch Panel Controller from overlapping the controller (Central remote controller, Network
convertor for Group remote controller and Network convertor for L
system.
● Indoor unit setting
SetD SetE SetF
63
06
0
SetD
Refrigerant
circuit address
REF AD X10 REF AD X1
IU AD X10
● RB unit setting
SetO SetP
63
06
SetO
Refrigerant
circuit address
REF AD X10 REF AD X1
RB AD X10
● Wired, Simple remote controller (3-wire) setting
SetJ: Dual remote control
(SW2 of DIP Switch1)
● Network convertor for L
SetM: Convertor address
● Wired remote controller (2-wire) setting
SetF: 0(fixed)
®
W
is a maximum of 16.
ON
ORKS
®
W
) connected to the same VRF Network
ON
ORKS
- (07-06) -
SetE
SetF
Remote
Indoor unit
controller
address
address
IU AD X1
RC AD
SetP
RB unit
address
RB AD X1
W
setting
ORKS ®
ON