Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 156

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

Model name
Power source
Available voltage range
Cooling
Capacity
Heating
Input power
Static pressure range
Standard static pressure
Airflow rate
Fan
Type x Quantity
Motor output
Sound pressure level
Length
Fin pitch
Rows x Stages
Face Area
Heat exchanger
Pipe type (Material)
Fin
Material
Enclosure
Colour
Net
Dimensions
(H x W x D)
Gross
Net
Weight
Gross
Liquid
Connection
Gas
pipe diameter
Drain hose
NOTE: Large airflow duct (ARXN  GATH) type can be connected to VR-II / V-III / V-II series only.
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
ARXN18GATH
5.6
kW
6.3
W
154
Pa
50 to 100
Pa
3
m
/ h
2,280
(l / s)
(633)
W
dB(A)
35
mm
2
m
Type (Material)
Surface
treatment
mm
kg
mm
- (04-17) -
ARXN24GATH
ARXN30GATH
ARXN34GATH
230 V ~, 50 Hz
198 to 264 V
7.1
9.0
10.0
8.0
10.0
11.2
205
306
432
50 to 150
50 to 250
50
2,640
3,200
3,720
(733)
(889)
(1,033)
Sirocco × 2
700 × 2
37
40
43
1,250
1.45
4 × 18
0.50
Grooved H-pin (Copper)
Slit (Aluminium)
Hydrophilic coating
galvanized sheet iron
-
450 × 1,587 × 700
520 × 1,750 × 825
84
100
ø 9.52 (Flare)
ø 15.88 (Flare)
VP25 [ø 25(I.D.) ; ø 32(O.D.)]
ARXN36GATH
ARXN45GATH
11.2
12.5
12.5
14.0
572
50 to 300
60
4,120
(1,145)
45
ø 19.05 (Flare)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents