Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 753

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

„ MEDIUM STATIC PRESSURE DUCT TYPE
Downward gradient
1/100 or more
Attached drain hose
Attached band
Trap
There is a drain port on the left and right sides. Select the drain port to match the local
conditions.
● Always check that the drain cap is installed to the unused drain port and is fastened with
the nylon fastener.
● If the drain cap is not installed, or is not sufficiently fastened by the nylon fastener, water
may drip during the cooling operation.
Prohibited
Rise
Drain port
CAUTION
- (06 - 62) -
Arrange the drain hose
lower than this position
1.5m to 2.0m
Air bleeding
Drain cap
Nylon fastener
Supporter