Fujitsu AIRSTAGE J-III L AJ 072LELAH Series Design & Technical Manual page 795

Hide thumbs Also See for AIRSTAGE J-III L AJ 072LELAH Series:
Table of Contents

Advertisement

z Touch panel controller setting (Set G)
*1 : Set Touch panel controller address first, to conduct the initial setting of it.
Refer to the "setting manual" for details.
*2 : The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote
controller and Network convertor for LONWORKS® is a maximum of 16.
z Network convertor setting (Set H)
*1 : Set the Rotary SW 110 and SW 111 on network convertor PCB.
*2 : The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote
controller and Network convertor for LONWORKS® is a maximum of 16.
*3 : Up to 64 Group remote controllers are able to connect with one VRF Network system.
*4 : When connecting the Network convertor for Single split AC , set up the number so that the Refrigerant circuit
address number of outdoor unit and indoor unit does not overlap .
And the sum total of the Refrigerant circuit address of Network convertor for Single split AC and the Refriger-
ant circuit address of the outdoor unit and the indoor unit is a maximum of 100.
00
Touch panel controller (Max. 16) *2
00
Network
convertor for Group
remote controller
(Max.16) *2
51
Network
convertor for
Single split AC
(Max.100) *4
- (07-14) -
01
02
03
Group remote controller (Max. 4)*3
Single split AC