6. CAPACITY COMPENSATION COEFFICIENT

„ COMPENSATION COEFFICIENT OF PIPE LENGTH
The tables give the compensation coefficient of pipe length owing to installation position (pipe
length, height difference). Pipe length and height difference are the length and the height
difference between outdoor unit and indoor unit.
z Cooling
Outdoor unit
(Upper)
50
40
30
20
10
0
10
20
0
- 10
- 20
- 30
- 40
Outdoor unit
(Lower)
z Heating
Outdoor unit
(Upper)
50
40
30
20
10
0
0
10
20
-10
-20
-30
-40
Outdoor unit
(Lower)
„ COMPENSATION COEFFICIENT OF FROSTING / DEFROSTING
(HEATING OPERATION)
To take the effects of accumulated frost and defrosting operation on heating capacity into
consideration, the capacity of outdoor unit should be corrected by compensation coefficient
shown in the table below.
Outdoor temperature
(°CDB / °CWB)
Compensation coefficient
30
40
50
60
70
30
40
50
60
70
-15 / -16
-9 / -10
-7 / -8
0.96
0.94
0.92
- (02 - 29) -
Pipe length
L (m)
80
90
100
110
120
Pipe length
L (m)
80
90
100
110
120
-5 / -6
-3 / -4
0 / -1
0.89
0.86
0.83
2 / 1
5 / 4
7 / 6
0.84
0.90
1.00