1-4. Wiring system

• Wiring configuration of the control system is made of power source wiring, transmission wiring,
and remote controller wiring.
• Total wiring length (total length of transmission line) can be extended up to 3,600 m by using sig-
nal amplifier.
To outdoor units
(Remote / Monitoring side)
Touch Panel Controller
One Touch panel controller can control
up to 400 groups / 400 indoor units.
Central Remote Controller
Maximum 100 indoor units can be controlled
BACnet Gateway
BACnet
UTY-ABGXZ1
BACnet
BACnet Operator
Workstation (B-OWS)
Modbus Convertor UTY-VMGX
Modbus
Network Convertor UTY-VLGX
L
W
ON
ORKS
Transmission Line
line is non-polar 2-conductor.
UTY-VSGXZ1
Web Monitoring Tool
Trouble free operation at all times
by remote monitoring system.
Internet
(Monitoring side)
(Monitoring side)
Combination of individual remote controller
Wired, simple and wireless remote controllers can be used jointly.
1-4. Wiring system
System Controller UTY-APGXZ1 or System Controller Lite UTY-ALGXZ1
• Maximum 1,600 indoor units can be controlled. *1
• Air conditioning control
• Operation monitoring
• Status monitoring system
• Electricity charge calculation *2
USB Adaptor
NW1
NW2
*3
Internet
NW3
*3
NW4
*3
Network Convertor
UTY-VGGXZ1
USB
Adaptor
Remote controller line (3-wire)
Maximum 16 units can be controlled
Modbus
network
System without Remote Controller
Together with Touch panel controller, it is
possible to build non remote controller system.
L
W
ON
ORKS
network
Web Monitoring Tool
UTY-AMGXZ1
USB
Adapter
Service Tool
UTY-ASGXZ1
(VRF network system side)
USB Adapter
Service Tool
Extensive monitoring and analysis
functions for installation and maintenance.
(Monitoring side)
Public Telephone Line
Group Remote Controller
Maximum 8 remote controller groups can be
controlled
Remote controller line (2-wire)
Maximum 16 units can be controlled
2 Remote Controllers
Indoor unit can be controlled
from both remote controllers.
Network Convertor
UTY-VTGX or UTY-
VTGXV or UTY-VGGXZ1
Multi system
Indoor unit
Touch Panel
(Cassette)
Controller
Central Remote
Indoor unit
Controller
(Duct)
Group Remote
RB unit
Controller
(Single)
Wired Remote
RB unit
Controller
(Multi)
- (05-12) -
Max. Transmission
line length
3,600 m
(Remote / Monitoring side) *2
Internet
or
Case of UTY-ALGXZ1
*1: Maximum 400 indoor units can be controlled.
*2: Option is necessary.
*3: Can not be used.
Internet
Smart device
Wireless LAN Adapter
Remotely manage an Air Conditioning
system using all sort of mobile devices
such as Smartphones, and tablets.
IR Receiver Unit
Duct type indoor unit
can be controlled
with wireless remote
controller.
Card key
External Switch Controller
Indoor units can be controlled by combining
with Card-key switch such as hotel room.
Network Convertor
UTY-VTGX or UTY-
VTGXV or UTY-VGGXZ1
Single system
Transmission line
Simple Remote
Controller
Module link
Remote controller
Simple Remote
line (3-line)
Controller
Remote controller
Simple Remote
line (2-line)
Controller
USB cable
Wireless Remote
Signal line
Controller
(single system)
External Switch
Controller
IR Receiver unit
1. Control system

Advertisement

Table of Contents
loading

This manual is also suitable for:

Airstage j-ivs aj 054lcldh seriesAirstage j-ivs aj 045lcldh seriesAirstage j-ivs auxb004glehAirstage j-ivs auxb007glehAirstage j-ivs auxb009glehAirstage j-ivs auxb012gleh ... Show all

Table of Contents