3. CC-Link COMMUNICATION FUNCTIONS

3.2.4 Communication baudrate setting

Set the transfer baudrate of CC-Link with the transfer baudrate switch (RSW1) on the option unit MR-
J2S-T01 front. The initial value is set to 156kbps.
The overall distance of the system changes with the transfer speed setting. For details, refer to the CC-
Link system master/local unit user's manual.

3.2.5 Occupied station count setting

Set the number of occupied stations with the occupied station count switch (SW1) on the option unit MR-
J2S-T01 front. The usable I/O signals and the number of connectable units change with the set number of
occupied stations. Refer to Section 3.2.3. In the initial status, the number of stations occupied is set to 1.
RSW3
0 (initial value)
SW1 setting
Number of occupied stations
1 station occupied
OFF
OFF
(Initial value)
OFF
2 stations occupied
ON
3 - 6
No.
Baudrate
156kbps
1
625kbps
2
2.5Mbps
3
5Mbps
4
10Mbps
5 to 9
Not used