3. CC-Link COMMUNICATION FUNCTIONS

3.2.3 Station number setting

(1) How to number the stations
Set the servo station numbers before powering on the servo amplifiers. Note the following points when
setting the station numbers:
(a) Station numbers may be set within the range 1 to 64.
(b) One servo amplifier occupies 1 or 2 stations. (One station of PLC remote device station)
(c) Max. number of connected units: 42
Note that the following conditions must be satisfied:
{(1 a)
(2 B)
a: Number of 1-station occupying units
b: Number of 2-station occupying units
c: Number of 3-station occupying units (not available for MR-J2S-CP-S084)
d: Number of 4-station occupying units (not available for MR-J2S-CP-S084)
{(16 A)
(54 B)
A: Number of remote I/O stations 64
B: Number of remote device stations 42
C: Number of local stations 26
(d) When the number of units connected is 4, station numbers can be set as shown below:
CC-Link
master unit
(2) Station number setting method
Set the station number with the station number switches (RSW1, RSW2) on the option unit MR-J2S-
T01 front. The station number that may be set is any of 1 to 64 in decimal. In the initial status, the
station number is set to station 1.
(3 d)
(4 d)} 64
(88 C)} 2304
PLC remote I/O
station
(1 station occupied)
Remote device station
Station No.1
RSW1
RSW2
Servo amplifier No.1
(When 2 stations are
occupied)
Station No.2
Set the tens. (initial value: 0)
Set the units. (initial value: 1)
3 - 5
Servo amplifier No.2
(When 2 stations are
occupied)
Remote device station
Station No.4
Number of connected units is 4.
Servo amplifier No.3
(When 2 stations are
occupied)
Remote device station
Station No.6