12. TROUBLESHOOTING

12.4.2 Remedies for alarms

CAUTION
When an alarm occurs, the trouble (RX(n+1)A or RX(n+3)A) switches on and the dynamic brake is
operated to stop the servo motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The
optional servo configuration software may be used to refer to the cause.
Display
Name
AL.10
Undervoltage
AL.12
Memory error 1 RAM, memory fault
AL.13
Clock error
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
If an absolute position erase alarm (AL.25) occurred, always make home position
setting again. Otherwise, misoperation may occur.
POINT
When any of the following alarms has occurred, always remove its cause
and allow about 30 minutes for cooling before resuming operation. If
operation is resumed by switching control circuit power off, then on to reset
the alarm, the servo amplifier and servo motor may become faulty.
Regenerative error (AL.30)
Overload 1 (AL.50)
Overload 2 (AL.51)
The alarm can be deactivated by switching power off, then on press the
"SET" button on the current alarm screen or by turning on the reset
(RY(n+1)A or RY(n+3)A). For details, refer to Section 12.4.1.
Definition
Power supply
1. Power supply voltage is low.
voltage dropped.
2. There was an instantaneous
MR-J2S- CP-S084:
control power failure of 60ms or
160VAC or less
longer.
MR-J2S- CP1-S084:
3. Shortage of power supply capacity
83VAC or less
caused the power supply voltage to
drop at start, etc.
4. Power was restored after the bus
voltage had dropped to 200VDC.
(Main circuit power switched on
within 5s after it had switched off.)
5. Faulty parts in the servo amplifier
Alarm (AL.10) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
Faulty parts in the servo amplifier
Printed board fault
Alarm (any of AL.11 to 13 and 15)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
Cause
Checking method
Checking method
12 - 5
Action
Review the power supply.
Change the servo amplifier.
Change the servo amplifier.