Universal Robots UR3 Service Manual page 202

Hide thumbs Also See for UR3:
Table of Contents

Advertisement

C720A0
Reset due to Low
Voltage Dectection
(LVD) or power off
C720A1
Low Voltage warning
level reached
C740A
Hardware monitoring
C740A0
Critical error
C740A1
1V2 voltage is
outside of the
allowed range
C740A2
1V8 voltage is
outside of the
allowed range
C740A3
2V5 voltage is
outside of the
allowed range
C740A4
3V3 voltage is
outside of the
allowed range
C740A5
PC 3V3 voltage is
outside of the
allowed range
C740A6
uA's 3V3voltage is
outside of the
allowed range
C740A7
uB's 3V3 voltage is
outside of the
allowed range
C740A8
5V voltage is outside
of the allowed range
C740A9
12V voltage is
outside of the
allowed range
UR3
Voltage needed values is
not reaching the necessary
values to work. Out of range
Voltage needed values is
not reaching the necessary
values to work. Out of range
A critical error occurred
during hardware monitoring
196
7. Troubleshooting
Same as C720A
Same as C720A
a) Do a Complete rebooting
sequence
b) Update software
c) Contact your local
Universal Robots service
provider for assistance 
Same as C740A
Same as C740A
Same as C740A
Same as C740A
Same as C740A
Same as C740A
Same as C740A
Same as C740A
Same as C740A
Same as C740A
Service Manual