Control mode
4.3.1

Change the control method (Pr. 80, Pr. 81, Pr. 800)

Set when selecting the control method for Advanced magnetic flux vector control and General-purpose magnetic flux
vector control. The initial value is V/F control.
Select a control mode using Pr. 800 Control method selection.
Parameter
Name
Number
80
Motor capacity
81
Number of motor poles
Control method
800
selection
* Set a value other than "9999" in Pr. 80 and Pr. 81.
(1)
Setting of the motor capacity and the number of motor poles (Pr. 80, Pr. 81)
Motor specifications (motor capacity and number of motor poles) must be set to select Advanced magnetic flux vector
control or General-purpose magnetic flux vector control.
Set the motor capacity (kW) in Pr. 80 Motor capacity and set the number of motor poles in Pr. 81 Number of motor poles.
(2)
Selection of control method
Select the inverter control method for V/F control, Advanced magnetic flux vector control, and General-purpose magnetic
flux vector control.
Pr. 80, 81
Other than 9999
9999
(Pr. 80, Pr. 81 initial value)
* Control method is V/F control regardless of the setting value of Pr. 800 when "9999" is set in Pr. 80 Motor capacity or Pr. 81 Number of motor poles.
(3)
Control method switching by external terminals (X18 signal)
Use the V/F switchover signal (X18) to change the control method (between V/F control and Advanced magnetic flux
vector control (General-purpose magnetic flux vector control)) with external terminal.
Turn the X18 signal ON to change the currently selected control method (Advanced magnetic flux vector control or
General-purpose magnetic flux vector control) to V/F control.
For the terminal used for X18 signal input, set "18" in any of Pr. 178 to Pr. 184 (input terminal function selection) to assign the
function.
REMARKS
When V/F control is selected by V/F switchover (X18 signal), second function is also selected at the same time. Control between
V/F and Advanced (General-purpose) magnetic flux can not be switched while the inverter is running. In case control is switched
between V/F and Advanced (General-purpose) magnetic flux, only second function is selected.
NOTE
Changing the terminal assignment using Pr. 178 to Pr. 184 (input terminal function selection) may affect the other
functions. Make setting after confirming the function of each terminal.
Parameters referred to
Advanced magnetic flux vector control
General-purpose magnetic flux vector control
Pr. 178 to Pr. 184 (input terminal function selection)
Pr. 450 Second applied motor
Pr. 44 Second acceleration/deceleration time, Pr. 45 Second deceleration time
Pr. 46 Second torque boost
Pr. 47 Second V/F (base frequency)
Pr. 48 Second stall prevention operation current
Pr. 51 Second electronic thermal O/L relay
76
Initial
Setting Range
Value
9999
9999
20
Pr. 800 Setting
20
Advanced magnetic flux vector control
(Pr. 800 initial value)
30
General-purpose magnetic flux vector control
— ∗
Refer to page 78
Refer to page 81
Refer to page 130
Refer to page 110
Refer to page 77
Refer to page 90
Refer to page 84
Refer to page 108
0.1 to 15kW
Set the applied motor capacity.
9999
V/F Control
2, 4, 6, 8, 10
Set the number of motor poles.
9999
V/F Control
Advanced magnetic flux vector control ∗
20
V/F
General-purpose magnetic flux vector control ∗
30
Control
Control Method
V/F control
Refer to page 101
Description