Idn11 Class 1 Diagnostic (C1D) - Kollmorgen Sercos II Translation Of The Original Manual

Fieldbus interface for s300 / s700
Table of Contents

Advertisement

®
sercos
IDN Set
3.13

IDN11 Class 1 Diagnostic (C1D)

The present fault status of the amplifier. When a fault occurs, the amplifier decelerates to
a stop and is disabled. The C1D status bit (AT bit 13) is set, and the corresponding fault
bits are set within IDN11. All faults are latched within IDN11 and are reset through the
"Procedure: Reset Class 1 Diagnostic" (IDN99). IDN99 performs a coldstart automatically
when required. A coldstart automatically results in the loss of communication. Those
faults which require a coldstart are noted in the table below. The error messages which
are displayed with LEDs on the front panel of the servo amplifier are also shown below.
LSB 0
MSB 15 Manufacturer-defined fault (IDN129).
Data Length: 2 bytes
Data Type:
Minimum:
Maximum:
Default:
26
Bit
Description
Overload fault (IDN114).
1
Amplifier over temperature fault (IDN203).
2
Motor over temperature fault.
3
Cooling system fault (IDN205).
4
Control voltage fault (±15V).
5
Feedback loss fault.
6
Commutation fault. Set to 0.
7
Overcurrent fault.
8
Overvoltage fault.
9
Undervoltage fault.
10
Power supply phase fault.
11
Excessive position deviation (IDN159).
12
Communication interface fault (IDN14).
13
Software limit switch fault (IDN49 and 50).
14
Reserved. Set to 0.
Binary
0
04/2016
Non-Volatile:
Write Access:
Run-Up Check:
Cyclic Transfer:
ASCII Param.:
Kollmorgen
Coldstart
Error
no
F15
no
F01
yes
F06
no
F13
yes
F07
yes
F04
yes
F25
yes
F14
no
F02
no
F05
yes
F12, F19
no
F03
no
F29
no
F24
IDN129
No
Read-only
AT
ERRCODE
®
sercos
for S300/S700