Idn49 Positive Position Limit; Idn50 Negative Position Limit; Idn51 Position Feedback Value 1 (Motor Feedback); Idn52 Reference Distance 1 (Motor Feedback) - Kollmorgen Sercos II Translation Of The Original Manual

Fieldbus interface for s300 / s700
Table of Contents

Advertisement

Kollmorgen
3.42

IDN49 Positive Position Limit

This IDN defines the maximum permissible position in the positive direction. The position
limit switch is active when IDN55 bit 4 or IDNP3004 is set. If linear scaling is selected in
IDN76, the limit switch is automatically calculated with the feed constant IDN123 and
enabled with the enable bit in IDN55. When the position setpoint reaches the limit switch,
the drive decelerates to a stop and error "F24" and warning "n07" flash in the LED. In
addition, fault bit 13 is set in IDN11 and the warning bit is set in IDN323 and IDN12 bit 13.
With linear position scaling the maximum value is 1024 x feed constant (IDN123).
Data Length: 4 bytes
Data Type:
Minimum:
Maximum:
Default:
Units:
3.43

IDN50 Negative Position Limit

This IDN defines the maximum permissible position in the negative direction. See IDN 49.
Data Length: 4 bytes
Data Type:
Minimum:
Maximum:
Default:
Units:
3.44

IDN51 Position Feedback Value 1 (Motor Feedback)

The master retrieves the motor's position feedback from the amplifier through IDN51. The
scaling type and the resolution will be defined within IDN76, 77, 78 and 79.
Data Length: 4 bytes
Data Type:
Minimum:
Maximum:
Default:
Units:
3.45

IDN52 Reference Distance 1 (Motor Feedback)

The distance from the machine zero point to the home position, referenced through the
motor feedback.
Data Length: 4 bytes
Data Type:
Minimum:
Maximum:
Default:
Units:
®
sercos
for S300/S700
04/2016
Signed decimal
31
-2
+1
31
2
-1
0
IDN76, 77, 78, 79, 123
Signed decimal
31
-2
+1
31
2
-1
0
IDN76, 77, 78, 79, 123
Signed decimal
IDN76, 77, 78, 79, 123
Signed decimal
31
- 2
+ 1
31
+ 2
- 1
0
IDN76, 77, 78, 79, 123
Non-Volatile:
YES
Write Access:
CP2, CP3, CP4
Run-Up Check:
Cyclic Transfer:
ASCII Param.:
SWE2
Version:
Non-Volatile:
YES
Write Access:
CP2, CP3, CP4
Run-Up Check:
Cyclic Transfer:
ASCII Param.:
SWE1
Version:
Non-Volatile:
No
Write Access:
Read-only
Run-Up Check:
Cyclic Transfer:
AT
ASCII Param.:
PFB
Version:
Non-Volatile:
Yes
Write Access:
CP2, CP3, CP4
Run-Up Check:
Cyclic Transfer:
ASCII Param.:
ROFFS
Version:
®
sercos
IDN Set
39