Table 49: Diagnostic Messages - WAGO 753-668/000-004 Manual

4fai 0/4-20 ma diff profisafe, fail-safe 4-channel analog input, 0/4-20 ma, differential inputs, profisafe for wago-i/o-system 750 series
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
753-668/000-004 4FAI 0/4-20 mA Diff PROFIsafe

Table 49: Diagnostic Messages

Alarm
Acknowledgement
required
Differing
F_Dest_Add
Discrepancy time
exceeded
Error downloading
the iParameters
Diagnostic
Module diagnostics
type
Coding
0x004F
LED indicator
PROFIsafe status green, 0.5 Hz flashing
Description/
Acknowledgement required to reactivate
Remedy
the channel or channels after error
correction. This diagnostic is only output
in PROFIsafe Module V2.6 mode.
Classification
Error
Diagnostic
Module diagnostics
type
Coding
0x0040
LED indicator
Group error red
PROFIsafe status red
Description/
The PROFIsafe address assigned as part
Remedy
of the F parameterization differs from that
set on the F I/O module. Check the DIP
switch setting or PROFIsafe address set
using the safety editor (SEDI).
Classification
Error
Diagnostic
Channel pair diagnostics
type
Coding
0x021E
LED indicator
Group error red
Description/
For two-channel analysis of the input pair,
Remedy
the F I/O module has determined that the
discrepancy time set has been exceeded.
Check the safety function. Adjust the
discrepancy time setting if necessary.
Classification
Error
Diagnostic
Module diagnostics
type
Coding
0x004A
LED indicator
No indicator
Description/
Timeout when writing (downloading) the
Remedy
iParameters from the iPar server. Check
whether an iPar server instance was
created for the F I/O module and whether
an appropriate data set exists.
Classification
Error
Version 1.0.0, valid from HW/SW Version 01/01
Diagnostics 121