ANL-24-L (24-Port Analog Line)
Station Present Test (or Ringing Application Test)
(#48)
This test applies momentary ringing voltage to the terminal equipment and
monitors resulting current flow to determine whether terminal equipment is
connected to the port. This test may cause some terminal equipment to ring
briefly during daily maintenance. If this ringing disturbs the customer or the
terminal equipment, you can disable it via the Tests field on the change station
form. However, on some software releases, Tests #6, 7, 161, and 35 are
disabled.
Table 8-31. Test #48 Station Present Test
Error
Test
Code
Result
Description / Recommendation
ABORT
Could not allocate the necessary system resources to run this test.
1. Retry the command at 1-minute intervals up to 5 times.
1000
ABORT
System resources required to run this test are not available. The port may be
busy with a valid call.
1004
ABORT
The port was seized by a valid call during the test. The test has been aborted.
1. Use the display port UUCSSpp command to determine the station
2. Use the status station command to determine the service state of the
3. If the port is active, wait until it is idle, and retry the command at 1-minute
1005
ABORT
The test was aborted due to a configuration problem. This test may not be
applicable or it may be disruptive to terminal equipment other than a voice
terminal (for example, the modem pool member or Music On Hold).
1008
ABORT
Could not allocate a ringing circuit. Either every ringing circuit is active, or the
ringing generator is either defective or incorrectly wired.
1. Retry the command at 1-minute intervals up to 5 times.
2. If the test continues to abort, look for RING-GEN errors in the Error Log. If
1018
ABORT
The test has been disabled by administration.The default for the
the station form is y. Determine why this field has been set to n on this station
(this may be due to the brief ringing disturbance that this test may cause).
1. To enable the test for a particular station being tested, enter change
555-233-143
extension.
port.
intervals up to 5 times.
an ABORT 1008 occurs for this test on other circuit packs as well, then the
ringing generator may be defective or is incorrectly wired (see errors for
RING-GEN). If it does not occur on other ports, then all four ring phases
are active.
station extension and set the
Test?
field on the station from
Continued on next page
Issue 1 May 2002
Test
field on
n
to y.
8-75