Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
LUNA2000-2.0MWH Series Smart String ESS User Manual About This Document About This Document Purpose This document describes the installation, electrical connections, commissioning and troubleshooting of LUNA2000-2.0MWH-1H0, LUNA2000-2.0MWH-2H0, LUNA2000-2.0MWH-1H1, LUNA2000-2.0MWH-2H1 and LUNA2000-2.0MWH- HE2H1 Smart String Energy Storage Systems (also referred to as ESS). Before installing and operating the ESS, ensure that you are familiar with the features, functions, and safety precautions provided in this document.
Page 4
LUNA2000-2.0MWH Series Smart String ESS User Manual About This Document Change History Changes between document issues are cumulative. The latest document issue contains all updates made in previous issues. Issue 15 (2023-11-01) Updated 2.1 Model Description. Updated 2.6.4.4 Extinguishant Control Panel.
Page 5
LUNA2000-2.0MWH Series Smart String ESS User Manual About This Document Issue 10 (2023-03-30) Updated 1 Safety Information. Updated 4.1 Site Selection Requirements. Updated 4.3 Foundation Requirements. Issue 09 (2023-02-20) Updated 1 Safety Information. Updated 3 Transportation and Storage. Updated 4.1 Site Selection Requirements.
Page 6
LUNA2000-2.0MWH Series Smart String ESS User Manual About This Document Updated 10.5 Powering Off the ESS. Updated 13.7 How Do I Perform a Dielectric Voltage Withstand Test on the AC Side of an ESS?. Updated 14 Technical Specifications. Issue 07 (2022-06-30) Updated 4.3 Foundation...
Page 7
LUNA2000-2.0MWH Series Smart String ESS User Manual About This Document Updated 10 Powering Off the System. Updated 11 Alarm Reference. Updated 13.6 What Should I Do If the ESU Cable Connection Detection Abnormal Alarm Is Generated on the WebUI?. Updated 12-Technical Data.
LUNA2000-2.0MWH Series Smart String ESS User Manual Contents Contents About This Document........................ ii 1 Safety Information........................1 1.1 Personal Safety..................................2 1.2 Electrical Safety..................................4 1.3 Environment Requirements..............................8 1.4 Mechanical Safety.................................10 1.5 Equipment Safety.................................. 15 1.5.1 ESS Safety.....................................15 1.5.2 Battery Safety..................................16 2 Overview..........................
Page 9
LUNA2000-2.0MWH Series Smart String ESS User Manual Contents 2.6.3.3 Air Conditioner in the Battery Cabin........................63 2.6.3.4 Electrode Water Sensor..............................64 2.6.3.5 Door Status Sensor................................ 65 2.6.3.6 Light....................................66 2.6.4 Fire Suppression System..............................66 2.6.4.1 CO Sensor..................................67 2.6.4.2 Air Exhaust Module............................... 68 2.6.4.3 Air Exhaust Controller..............................
Page 10
LUNA2000-2.0MWH Series Smart String ESS User Manual Contents 5.4.1 Installing Copper Bars Between Battery Packs..................... 125 5.4.2 (Optional) Filling the Fire Cylinder with Extinguishant..................130 5.4.3 Installing the Battery in the Extinguishant Control Panel................133 6 Installing Cables........................137 6.1 Preparing Cables................................. 137 6.2 Connecting Socket Circuit Wires...........................
Page 11
LUNA2000-2.0MWH Series Smart String ESS User Manual Contents 13.5 Why Does the PSU Not Start After the Water and Fire Alarms Are Cleared..........200 13.6 What Should I Do If the ESU Cable Connection Detection Abnormal Alarm Is Generated on the WebUI?......................................
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information Safety Information Statement Before transporting, storing, installing, operating, using, and/or maintaining the equipment, read this document, strictly follow the instructions provided herein, and follow all the safety instructions on the equipment and in this document.
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● The equipment is installed or used in environments that do not comply with international, national, or regional standards. ● The equipment is installed or used by unqualified personnel. ●...
Page 14
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information WARNING During operations, wear personal protective equipment such as protective clothing, insulated shoes, goggles, safety helmets, and insulated gloves. Figure 1-1 Personal protective equipment General Requirements ● Do not stop protective devices. Pay attention to the warnings, cautions, and related precautionary measures in this document and on the equipment.
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information – Trained personnel: personnel who are trained in technology and safety, have required experience, are aware of possible hazards on themselves in certain operations, and are able to take protective measures to minimize the hazards on themselves and other people ●...
Page 16
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information CA UTION Do not route cables near the air intake or exhaust vents of the equipment. General Requirements ● Follow the procedures described in the document for installation, operation, and maintenance. Do not reconstruct or alter the equipment, add components, or change the installation sequence without permission.
Page 17
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● If fault diagnosis and troubleshooting need to be performed after power-off, take the following safety measures: Disconnect the power supply. Check whether the equipment is live. Install a ground cable. Hang warning signs and set up fences.
Page 18
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● Secure buried cables using cable supports and cable clips. Ensure that the cables in the backfill area are in close contact with the ground to prevent cable deformation or damage during backfilling.
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information Figure 1-2 Wearing an ESD wrist strap ● When holding a board or a module with exposed circuit boards, hold its edge without touching any components. Do not touch the components with bare hands.
Page 20
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information WARNING Install the equipment in an area far away from liquids. Do not install it under areas prone to condensation, such as under water pipes and air exhaust vents, or areas prone to water leakage, such as air conditioner vents, ventilation vents, or feeder windows of the equipment room.
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information top of the equipment to prevent foreign objects from falling into the equipment. ● When installing the equipment, ensure that the installation surface is solid enough to bear the weight of the equipment.
Page 22
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information WARNING When pulling equipment out of a cabinet, be aware of unstable or heavy objects in the cabinet to prevent injury. WARNING Do not drill holes into the equipment. Doing so may affect the sealing performance and electromagnetic containment of the equipment and damage components or cables inside.
Page 23
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● Do not quickly lift a heavy object above your waist. Place the object on a workbench that is half-waist high or any other appropriate place, adjust the positions of your palms, and then lift it.
Page 24
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● Do not pile up scaffolding, springboards, or other objects on the ground under the area involving working at heights. Do not allow people to stay or pass under the area involving working at heights.
Page 25
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● Ensure that the foundation where hoisting is performed on meets the load- bearing requirements. ● Before hoisting objects, ensure that hoisting tools are firmly secured onto a fixed object or wall that meets the load-bearing requirements.
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● High-temperature pipes after welding must be promptly cooled. Using a Jack ● A hydraulic jack is used to lift the container. Load bearing requirement: 30 t ● Only one side of the equipment can be raised or lowered. Before applying force, place wood sleepers and pads and take measures to prevent the jack from slipping and the equipment from vibrating.
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information NO TICE Take protection and isolation measures for the ESS, such as installing fences, walls, and safety warning signs to prevent personal injury or property damage caused by unauthorized access during operations.
Page 28
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information D ANGER To avoid leakage, smoke, flammable gas release, thermal runaway, fire, or explosion, do not disassemble, alter, or damage batteries, for example, insert foreign objects into batteries, squeeze batteries, or immerse batteries in water or other liquids.
Page 29
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information WARNING Install batteries in a dry area. Do not install them under areas prone to water leakage, such as air conditioner vents, ventilation vents, feeder windows of the equipment room, or water pipes. Ensure that no liquid enters the equipment to prevent faults or short circuits.
Page 30
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information Statement The Company shall not be liable for any damage or other consequences to the batteries it provides due to the following reasons: ● Batteries are damaged due to force majeure such as earthquakes, floods, volcanic eruptions, debris flows, lightning strikes, fires, wars, armed conflicts, typhoons, hurricanes, tornadoes, and other extreme weather conditions.
Page 31
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information General Requirements NO TICE To ensure battery safety and battery management accuracy, use batteries provided by the Company. The Company is not responsible for any faults of batteries not provided by it.
Page 32
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information ● If batteries are left unused for a long period of time, store and charge them according to the battery requirements. ● Do not charge or discharge batteries by using a device that does not comply with local laws and regulations.
Page 33
LUNA2000-2.0MWH Series Smart String ESS User Manual 1 Safety Information Recycling ● Dispose of waste batteries in accordance with local laws and regulations. Do not dispose of batteries as household waste. Improper disposal of batteries may result in environmental pollution or an explosion.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Overview 2.1 Model Description Product Models This document involves the following product models: ● LUNA2000-2.0MWH-1HX ● LUNA2000-2.0MWH-2HX ● LUNA2000-2.0MWH-HE2HX NO TE [1]: The number corresponding to X is on the nameplate.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Meaning Description Backup power ● 1HX: Applies to scenarios where the backup duration is greater than or equal to 1 hour ● 2HX: Applies to scenarios where the backup duration is greater than or equal to 2 hours Note [1]: The nominal capacity is on the nameplate.
2.3 Functions and Features Functions The LUNA2000-2.0MWH series Smart String ESS (excluding the Smart PCS) can manage charge and discharge of the DC power rectified by the Smart PCS for power grid peak shaving and frequency regulation. Issue 15 (2023-11-01)
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Features The ESS is a prefabricated all-in-one energy storage system that integrates the prefabricated modular structure system, power supply and distribution system, monitoring system, environment control system, fire suppression system, and integrated cabling system.
Page 38
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Number of Number of Number Number Numbe Conditioner DC Circuit Smart Rack of Mixed- r of Position in the Breakers in Controllers Exhaust Flow Pressur Battery Cabin the Control Fans Fans...
Page 39
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-4 Components of the LUNA2000-2.0MWH-1HX LUNA2000-2.0MWH-2HX NO TE The LUNA2000-2.0MWH-2HX models have multiple layouts. The figures use two layouts as examples. For details, see the following table. Table 2-3 LUNA2000-2.0MWH-2HX layouts...
Page 43
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-8 Components of the LUNA2000-2.0MWH-2HX (2) LUNA2000-2.0MWH-HE2HX Table 2-4 LUNA2000-2.0MWH-HE2HX layout Number Number Numb Numbe Number of Conditione of DC of Smart er of r of Pressure Relief r Position...
Page 46
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-12 LUNA2000-2.0MWH-2HX/LUNA2000-2.0MWH-HE2HX battery cabin configurations 1 Table 2-5 Battery cabin configurations 1 Component Configuration Quantity Description Configured Name for an ESS Door status Mandatory Monitors the door sensor status of the battery cabin.
Page 48
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Table 2-6 Battery cabin configurations 2 Component Configuration Quantity Description Configured Name for an ESS Temperature Mandatory Detects the indoor temperature and humidity humidity in real time. (T/H) sensor Smoke Mandatory...
Page 49
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-14 Battery cabin configurations 3 Table 2-7 Battery cabin configurations 3 Component Configuration Quantity Description Configured for Name an ESS Air intake Mandatory Consists of the module labyrinth and air filter foam.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.5.2 Control Unit Cabin Figure 2-15 Control unit cabin component configuration 1 Table 2-8 Control unit cabin component configuration 1 Component Configuration Quantity Description Configured Name for an ESS Extinguishant Mandatory...
Page 51
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-16 Control unit cabin component configuration 2 Table 2-9 Control unit cabin component configuration 2 Component Configuration Quantity Description Configured for Name an ESS Door status Mandatory Monitors the door...
Page 52
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Component Configuration Quantity Description Configured for Name an ESS Extinguishant Mandatory Used for fire alarms control panel and automatic fire extinguishing control. For details, see the extinguishant control panel manual included with the ESS.
Page 54
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Table 2-10 Control unit cabin component configuration 3 Component Configuration Quantity Description Configured for Name an ESS DC circuit Mandatory ● LUNA2000-2. Provides short- breaker 0MWH-1HX: circuit protection and DC circuit disconnection.
Page 55
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Component Configuration Quantity Description Configured for Name an ESS Central Mandatory Aggregates monitoring interfaces, unit (CMU) converts protocols, collects, stores, and monitors data, and performs unified monitoring and local maintenance for devices in the ESS.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-21 Configuration of components in the Smart Rack Controller cabin of LUNA2000-2.0MWH-2HX/LUNA2000-2.0MWH-HE2HX Table 2-11 Configuration of components in the Smart Rack Controller cabin Component Configuration Quantity Description Configured for Name...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.6.1.1 Battery Pack NO TE The appearance of the battery pack is for reference only, and that of the actual product may vary. Figure 2-22 Appearance Technical Battery Pack Specifications Model...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Table 2-14 Technical specifications of bus side Technical Specifications Smart Rack Controller Number of battery strings connected to the bus Maximum DC voltage 1500 V Rated operating voltage 1200 V Rated working current of a single 143.3 A...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-24 Appearance (1) Ground screws (2) AC input module (3) LLVD power distribution (4) Monitoring module (5) BLVD power distribution (6) Battery wiring ports SMU02C (7) Reserved slot for the...
Page 62
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Appearance Figure 2-26 Appearance (1) Power indicator (2) Alarm indicator (3) Fault indicator (4) Locking latch (5) Handle Indicators Table 2-16 Indicator description Indicator Color Status Description Power Green Steady on The PSU has an AC input.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Indicator Color Status Description The PSU is hibernating. Blinking at The communication between the PSU 0.5 Hz and the monitoring module is interrupted. Fault The PSU is normal. indicator Steady on The PSU locks out due to output overvoltage.
Page 64
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Name Color Status Description Blinking The SMU is running properly and slowly (0.5 communicating with the host properly. Blinking fast The SMU is running properly but fails (4 Hz) to communicate with the host.
Page 65
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview The LCD supports two-level password management for different users. Table 2-19 Two-level password management Level Operation Permission Password Engineer All permissions except for 000001 changing the administrator password and resetting the...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Indicator Colo Status Description Blinking The SMU is running properly and slowly (0.5 communicating with the host properly. Blinking fast The SMU is running properly but fails (4 Hz) to communicate with the host.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.6.2.1 CMU Appearance Figure 2-29 Appearance (1) LED indicator (2) SIM card slot (3) Mounting ear (4) Guide rail clamp (5) MBUS port (reserved) (6) GE port (WAN) (7) SFP port...
Page 68
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Indicators Table 2-21 Indicators Indicator Status Description Running Green off Not powered on indicator Blinking green slowly (on for 1s The communication with (RUN) and then off for 1s) the management system is normal.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.6.2.2 SmartModule Appearance Figure 2-30 Appearance (1) LED indicator (2) Mounting ear (3) Guide rail clamp (4) COM port (5) DI port (6) 12 V output power port (7) AI port...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Indicators Indicator Status Description Running Green off Not powered on indicator Blinking green slowly (on for The communication with the (RUN) 1s and then off for 1s) CMU is normal. Blinking green fast (on for The communication with the 0.125s and then off for 0.125s)
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-31 Position of IO board (1) Position of IO Board Technical Specifications IO Board Model ENF1DETC Operating voltage 220 V AC/12 V DC/24 V DC Operating current ≤ 1 A Operating temperature –30°C to +55°C...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.6.3.1 T/H Sensor Figure 2-32 Appearance NO TE The appearance of the T/H sensor depends on the actual delivery. Table 2-22 T/H sensor technical specifications Technical Specifications T/H sensor Temperature measuring range –20°C to +80°C...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Table 2-23 Pin definitions of an RJ45 connector Description Pin 1 or Pin 4 Pin 2 or Pin 5 Pin 3 Pin 6 Reserved Pin 7 Reserved Pin 8 2.6.3.2 Air Conditioner in the Control Unit Cabin...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Specifications Air Conditioner in the Control Unit Cabin Heating capacity 1100 W Dimensions (H x W x D) ● 746 mm x 446 mm x 300 mm (without flanges) ● 783 mm x 479 mm x 300 mm (with flanges)
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Specifications Air Conditioner in the Battery Cabin Air conditioner model PC6H Rated voltage 208–230 V AC Rated cooling capacity ● 6350 W (L25/L45) ● 9300 W (L25/L35) Rated heating capacity...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-36 Appearance Technical Specifications Electrode Water Sensor Operating temperature –40°C to +80°C Storage temperature –40°C to +80°C 2.6.3.5 Door Status Sensor Figure 2-37 Appearance (1) Switch (2) Magnet Technical Door Status Sensor...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Door Status Sensor Specifications Switch voltage 100 V DC (Max) Contact withstand 150 V DC (Max) voltage Impedance 0.3 ohms Switch status Steady on Outer material White acrylonitrile butadiene styrene (ABS) engineering plastic 2.6.3.6 Light...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.6.4.1 CO Sensor CO sensor detects the concentration of CO in combustible gases. Figure 2-39 Appearance Table 2-24 Technical specifications of the CO sensor Technical Specifications CO Sensor Dimensions (H x W x D)
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Table 2-25 Pin definitions of an RJ45 connector Description Pin 1 or Pin 4 Pin 2 or Pin 5 Pin 3 Pin 6 Reserved Pin 7 Reserved Pin 8 V– 2.6.4.2 Air Exhaust Module The air exhaust module is the actuator of the active air exhaust system.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-42 Appearance (1) Power input ports (2) Fan ports (3) Indicators (4) Communications port 1 (5) Communications port 2 Table 2-26 Indicator description Silkscr Color Status Description Green Steady on Power supply to the board is normal but no program is running.
Page 81
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Model: K11031M2 Figure 2-43 Appearance Technical Extinguishant Control Panel Specifications Model K11031M2 Dimensions (H x 310 mm x 385 mm x 90 mm W x D) Operating voltage ● 230 V+10%/–15% AC ●...
Page 82
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Sealed Lead-Acid Battery Specifications Required CE or UL certification certification Complied IEC 61056 standard Model: JB-QBL-QM210 Figure 2-44 Appearance Technical Extinguishant Control Panel Specifications Model JB-QBL-QM210 Dimensions (H x 440 mm x 340 mm x 99 mm...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Extinguishant Control Panel Specifications Detector loop ● Wire system of the detector loop: two-wire system requirements ● Length of the detector loop: ≤ 1000 m Enclosure A3 steel material Installation mode...
Page 84
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-45 Appearance of a fire cylinder (1) Position of the electromagnetic valve after installation Technical Fire Cylinder Specificatio Model 227M38 SPS020- P000943 NCM38UF GQQ40/ YF40/2 UFAA MS-032B Operating 24 V DC...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Fire Cylinder Specificatio Electromag 24 V 24 V 24 V 24 V 24 V 24 V netic DC/0.6 DC/0.6 A DC/0.6 A DC/0.6 A DC/1 A DC/1 startup voltage/ current Operating -10°C to...
Page 86
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-46 Appearance Figure 2-47 Position of input/output modules (1) Position of input/output modules. Technical Specifications Input/Output modules Model KZJ-956 Cabling mode Non-polarized two-wire system Quiescent current <0.6 mA Operating current <10 mA...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Specifications Input/Output modules Working status indication ● The indicator blinks about every 12 seconds in the inspection state, and is steady on in the output state. ● The input indicator is steady on in the input state.
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-49 Position of the fire signal transfer board (1) Position of the fire signal transfer board Technical Specifications Fire Extinguishing Board Model ENF1DETAA Operating voltage 24 V Operating current ≤ 1 A Operating temperature –30°C to +55°C...
Page 89
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Table 2-27 Indicator description Item Color Status Description Indicators Steady on Enters alarm status Blinking Enters monitoring status Table 2-28 Technical specifications of the heat detector Technical Heat Detector Specifications Configuring model...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Heat Detector Specifications IP rating IP54 IP30 2.6.4.9 Smoke Detector The smoke detector can detect the smoke concentration in the environment. CA UTION Do not use smoke detectors in condensation scenarios. Otherwise, false alarms may be generated.
Page 91
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Specifications Smoke Detector Cabling mode Polarized two-wire system Operating current ● Power-up surge current: 115 μA at 24 V ● Alarm LED current: 4 mA Operating temperature –20°C to +60°C Humidity ≤...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.6.4.10 Fire Alarm Horn/Strobe Table 2-32 Indicator description Item Color Status Description Indicators Steady on Enters the alarm status. Blinking Enters the monitoring status. Model: 958CHL1001 Figure 2-52 Appearance Technical Specifications...
Page 93
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Specifications Fire Alarm Horn/Strobe IP rating IP33C Model: SG-993 Figure 2-53 Appearance Technical Specifications Fire Alarm Horn/Strobe Model SG-993 Operating voltage 24 V DC Operating current Monitoring status < 1 mA; alarm status <...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Technical Specifications Fire Alarm Horn/Strobe Cabling mode Non-polar two-line (L1, L2) + power cable IP rating IP30 2.6.4.11 Extinguishant Release Indicator Model: K27102 Figure 2-54 Appearance Technical Specifications Extinguishant Release Indicator...
Page 95
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Model: QM-ZSD-02 Figure 2-55 Appearance Technical Specifications Extinguishant Release Indicator Model QM-ZSD-02 Operating voltage 24 V + 24 V DC Operating current ● Bus current in static state: ≤ 500 µA ●...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview 2.6.4.12 (Optional) Water Sprinkler System The water sprinkler system is used to put out a fire in the ESS if the fire suppression system fails or the fire cannot be put out due to other uncontrollable factors.
Page 97
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-57 Water sprinkler system layout (1) Water sprinkler system layout Table 2-33 Port specifications Item Specifications External thread BSPT 2" Thread length 20 mm Table 2-34 Water inlet requirements Item...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Startup Requirements NO TICE ● Check that the extinguishant monitoring devices are connected to the plant control system. ● Check that the ambient temperature monitoring devices in the ESS are connected to the plant control system.
Page 99
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Table 2-35 Switch configuration Models Battery Smart Rack DC Circuit Conditio Conditioner Pack Fans Controller Breakers Switches No. Switches Switches No. in the Position Control in the Unit Battery Cabin Cabin...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Figure 2-64 Battery circuit diagram 3 of the LUNA2000-2.0MWH-2HX/ LUNA2000-2.0MWH-HE2HX 2.7.2 Working Modes The ESS has six working states: running, hibernation, self-check, fault, offline, and loading. Table 2-36 Working states Working...
LUNA2000-2.0MWH Series Smart String ESS User Manual 2 Overview Working Description State Self-check The ESS is in progress of a self-check. Fault If a Smart Rack Controller or a battery pack is faulty, the ESS enters the fault state. Offline Smart Rack Controllers are disconnected from the CMU.
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage Transportation and Storage 3.1 Transportation Requirements General Requirements ● Be cautious to prevent injury when moving heavy objects. ● If multiple persons need to move a heavy object together, determine the manpower and work division with consideration of height and other conditions to ensure that the weight is equally distributed.
Page 108
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage ● When moving a heavy object, be aware of the workbench, slope, staircase, and slippery places. When moving a heavy object through a door, ensure that the door is wide enough to move the object and avoid bumping or injury.
Page 109
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage ● Comply with the international regulations on the transport of dangerous goods and meet the requirements of the transportation regulatory authorities in the countries of departure, route, and destination.
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage 3.2 Storage Requirements General Requirements ● Proof that the product is stored according to the requirements must be available, such as temperature and humidity log data, storage environment photos, and inspection reports.
Page 111
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage Battery Storage Requirements WARNING ● Ensure that batteries are stored in a dry, clean, and ventilated indoor environment that is free from sources of strong infrared or other radiations, organic solvents, corrosive gases, and conductive metal dust.
Page 112
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage Label Description This way up: The package shall be vertically oriented during transport and storage. Fragile: The package contains fragile objects and shall be handled with care. Keep dry: The package shall be kept away from rain.
Page 113
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage Storage Temperature (T) Maximum Charge Interval –40°C < T ≤ +30°C 15 months 30°C < T ≤ 40°C 11 months 40°C < T < 60°C 7 months Note a: The interval starts from the latest charge time labeled on the battery package.
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage Power-Off SOC Before Storage Maximum Charge Interval SOC ≥ 50% Refer to the charge intervals for batteries delivered separately. 5% ≤ SOC < 50% 20 days SOC < 5% 48 hours ●...
Page 115
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage ● The following table lists the maximum charge intervals for batteries delivered separately. Charge the batteries promptly and calibrate the SOC to at least 50%. Otherwise, the battery performance and service life may be deteriorated.
Page 116
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage Inspection Before Charge Before charging a battery, you need to check its appearance. Charge the qualified battery or dispose of the unqualified one. The battery is qualified if it is free from the following symptoms: –...
Page 117
LUNA2000-2.0MWH Series Smart String ESS User Manual 3 Transportation and Storage Step 7 After the discharge and charge are complete, wait until the fan in the charger keeps running for about 5 minutes to dissipate the residual heat, turn off the AC and DC circuit breakers, and remove the cables.
LUNA2000-2.0MWH Series Smart String ESS User Manual 4 Site Requirements Site Requirements 4.1 Site Selection Requirements NO TICE Design code for electrochemical energy storage station , Refer to the GB 51048 Standard for the Installation of Stationary Energy Storage Systems , and NFPA 855 local laws and regulations.
Page 119
LUNA2000-2.0MWH Series Smart String ESS User Manual 4 Site Requirements ● It is recommended that outdoor open electrochemical energy storage plants be equipped with fences and walls. The external walls of an electrochemical energy storage plant deployed in a power plant or power transformation and distribution station shall be permitted to serve as the enclosure and isolation walls.
Page 120
LUNA2000-2.0MWH Series Smart String ESS User Manual 4 Site Requirements ● Areas with dust, oil fumes, harmful gases, corrosive gases, etc. ● Areas with corrosive, flammable, and explosive materials ● Areas with existing underground facilities ● Areas with adverse geological conditions such as rubbery soil and soft soil layer, or prone to waterlogging and land subsidence ●...
NO TE The foundation layout design should meet the space requirements for ESS installation and O&M. The design institute can contact local Huawei pre-sales engineers to obtain the drawings about the foundation. Before installation, build a concrete platform and trenches on the selected ground.
Page 122
LUNA2000-2.0MWH Series Smart String ESS User Manual 4 Site Requirements ● A cable trench (if any) cannot be used for drainage. Fire retardant sealing should be implemented at cable holes (such as holes through partition walls and floors). Check Item...
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Installation 5.1 Installation Preparations 5.1.1 Preparing Tools NO TE ● The tools shown in the figures are for reference only. ● The tool table may not list out some tools required onsite. Onsite installation personnel and the customer need to prepare the tools based on site requirements.
Page 124
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Wire strippers Diagonal pliers Utility knife Flat-head insulated torque screwdriver Cable cutter RJ45 crimping tool Vacuum cleaner Multimeter DC voltage measurement range ≥ 1500 V DC Marker Steel measuring Digital or bubble...
Page 125
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Rubber mallet Hammer drill Crane Hoisting rope and lifting eye Drill bit (φ14/φ16/ φ20) Personal Protective Equipment (PPE) Insulated gloves Protective gloves Safety goggles Dust mask Safety helmet Safety shoes Reflective vest...
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation 5.1.2 Installation Environment Check Check the site requirements one by one, and start installation only after all requirements are met. The Company will not be liable for any consequences in the case that the installation environment does not meet the requirements.
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Procedure Step 1 Determine the reference points for installing the ESS on the concrete platforms. Mark the reference points using a marker. Step 2 On the basis of the reference points, mark the mounting positions for the four corner fittings of the ESS using an ink fountain and a long soft measure tape.
Page 128
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation ● When installing or removing the hoisting equipment, do not drag it on the ESS to prevent scratches. Hoisting Precautions Table 5-1 Hoisting precautions Stage Precautions Before hoisting Ensure that the crane can hoist a load greater than 50 t, and the working radius is not less than 10 m.
Page 129
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation NO TE ● You are advised to level concrete platforms before hoisting the ESS. ● The horizontal error of concrete platforms cannot exceed 5 mm. ● Prepare and install the lifting eyes and steel ropes.
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation 5.3.3 Opening the Doors of the ESS CA UTION Do not open the container door in rainy, snowy, lightning, or dusty weather conditions. Procedure Step 1 Use a cable cutter to cut off the TSA approved lock on the door of the control unit cabin.
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation 5.3.4 Grounding the ESS Prerequisites WARNING Do not connect devices such as fuses and switches to ground cables. CA UTION The grounding should comply with the local electrical safety regulations. ●...
Page 133
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-5 Position of the ground cable hole and pagoda connector cutting (1) Ground cable hole NO TE The position for cutting the pagoda connector is for reference only. The actual cable usage may vary.
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-6 Installing ground cables ● Connect ground lugs to the ESS ground points using M12x30 stainless steel bolt assemblies. NO TE – Ground lug: Use ground lugs made of hot-dip zinc-coated flat steel sheet with a...
Page 135
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation CA UTION ● Place a wooden block on the top of an expansion bolt, and then knock at the wooden block using a claw hammer to avoid damaging the expansion bolt.
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Follow-up Procedure After the ESS is installed, verify the installation to ensure normal use of products and smooth subsequent installation. Table 5-3 Verifying the installation Check Item Check Method Criteria Bolts and nuts...
Page 137
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-9 Positions of the copper bars (1) Desiccan (Montmorillonite desiccant, 500 (2) Copper bar NO TE ● There are 25 desiccant bags, four bags for each battery rack in the battery cabin and one bag for the control unit cabin.
Page 138
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation CA UTION When installing copper bar C, keep away from communications cables and fan power cables of battery packs to prevent cables from being squeezed. NO TICE ● Use the copper bars delivered with the ESS. Do not use copper bars from ESSs of different models.
Page 139
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-11 Installing copper bars between battery packs NO TE For some models, each battery rack contains only 19 battery packs. Install copper bars by referring to the following figure. Issue 15 (2023-11-01)
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation 5.4.2 (Optional) Filling the Fire Cylinder with Extinguishant CA UTION ● This document does not provide details about how to fill the fire cylinder with extinguishant. Perform this operation in a dedicated station.
Page 142
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-13 Removal process diagram Step 7 Fill the fire cylinder with extinguishant. Table 5-4 Requirements Technical Specifications Values Extinguishant Heptafluoropropane Perfluorohexanone Extinguishant weight 26–27 kg 31–32 kg Purity requirement ≥ 99.9%...
Page 143
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Ambient Pressure Pressure Pressure Pressure Temperature (Bar) of (Bar) of (Bar) of (Bar) of (℃) 227M38UFAA SPS020- P0009438 NCM38UFAA MS-032B-EN 26.2 26.54 25.8 26.2 27.4 28.46 26.5 27.4 28.6 30.38 27.3 28.6...
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-14 Installation process diagram ----End 5.4.3 Installing the Battery in the Extinguishant Control Panel Prerequisites NO TICE ● The extinguishant control panel has been configured and commissioned before delivery. Non-professional personnel are prohibited from configuring the extinguishant control panel without permission.
Page 145
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-15 Position of the extinguishant control panel (1) Position of keys (2) Position of the extinguishant control panel Procedure CA UTION ● Do not damage components in the extinguishant control panel during the installation.
Page 146
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-16 Installing the battery in the extinguishant control panel Close the extinguishant control panel. Remove the key from the extinguishant control panel. NO TE Hand over the key to the responsible personnel for safekeeping.
Page 147
LUNA2000-2.0MWH Series Smart String ESS User Manual 5 Installation Figure 5-17 Installing the battery in the extinguishant control panel Close the extinguishant control panel. Remove the key from the extinguishant control panel. NO TE Hand over the key to the responsible personnel for safekeeping.
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Installing Cables D ANGER ● Do not smoke or have an open flame around batteries. ● The site must be equipped with qualified fire fighting facilities, such as fire sand and carbon dioxide fire extinguishers.
Page 149
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Table 6-1 Cable description Cable Type Conductor Cross- Outer Termin Source Sectional Area Range Diameter Two-core LUNA2000-2.0MWH-1 25–68 mm Prepared power outdoor copper/ OT/DT by the HX: 240–400 mm cable...
Page 150
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Cable Type Conductor Cross- Outer Termin Source Sectional Area Range Diameter CAT 5E outdoor < 9 mm Shielde Prepared commu shielded network d RJ45 by the nication cable, internal connect...
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables 6.2 Connecting Socket Circuit Wires Scenario 1 This procedure applies only to the models listed in the table below. Models Air Conditioner Position in the Battery Cabin LUNA2000-2.0MWH-1HX 1/3/5/7/9/11 LUNA2000-2.0MWH-2HX/ 1/4/7/10 LUNA2000-2.0MWH-HE2HX...
Page 152
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-4 Connecting the live wire and neutral wire from the mains (1) 110 V/220 V socket installing position Install the 110 V switch. Connect the live wire (corresponding to cable 2056) and neutral wire (corresponding to cable 2055) from the upper end of the switch to positions 1 and 2 of the XT9 terminal block.
Page 153
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Step 3 Connecting ground cables: Determine whether the socket ground cables are routed in from the top or bottom. NO TE Step 3 applies to the scenarios where a 220 V or 110 V socket is installed. The following figure uses a 220 V socket as an example.
Page 154
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-7 Routing the ground cables in from the bottom ----End Scenario 2 This procedure applies only to the models listed in the table below. Models Air Conditioner Position in the Battery Cabin LUNA2000-2.0MWH-1HX...
Page 155
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-8 Before installing the socket (1) Cable binding position Step 1 Select a 110 V or 220 V socket as required. Step 2 Connect the live wire and neutral wire.
Page 156
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-10 Connecting the live wire and neutral wire from the lower end of the switch ● Installing a 220 V socket Connect the live wire (corresponding to cable 1756) and neutral wire (corresponding to cable 1759) from the lower end of the switch to positions 1 and 3 of the XT1 terminal block.
Page 157
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-12 Connecting the live wires and neutral wires from the lower end of the terminal block Step 4 Connecting ground cables: Determine whether the socket ground cables are routed in from the top or bottom.
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-14 Routing the ground cables in from the bottom ----End 6.3 Installing DC Power Cables Prerequisites ● The ESS is not powered on. ● The DC power cables have been pre-buried according to the specifications.
Page 159
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Step 2 Remove the baffle plates for the DC power cables. Figure 6-16 Removing the baffle plates for the DC power cables Step 3 Connect the DC power cables. NO TICE ●...
Page 160
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-17 DC power cable positions at the bottom (1) DC power cable hole (2) AC input power cable or ground cable hole (3) Optical cable or FE communications cable...
Page 161
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-18 Connect the single-core DC power cables of LUNA2000-2.0MWH-1HX Figure 6-19 Connect the single-core DC power cables of LUNA2000-2.0MWH-2HX/LUNA2000-2.0MWH-HE2HX (1) Screw assembly (2) Spring washer (3) Large washer (optional)
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables (4) Wiring terminals (5) Copper bar (6) Flat washer Step 4 Install the removed cover. ----End 6.4 Installing AC Input Power Cables (With External Grid Power Supply) Prerequisites ● The ESS is not powered on.
Page 164
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-22 Removing the protective cover Step 2 Remove the baffle plates for the AC input power cables. Figure 6-23 Removing the baffle plates for the AC input power cables Step 3 Connect AC input power cables.
Page 165
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables NO TICE ● The screw assembly whose model is subject to the delivery should be tightened according to the corresponding standard torque. ● Partially tighten the nuts of the AC input power cables to a torque of 5 N·m when securing the cables.
Page 166
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-25 Connecting the four-core AC input power cables (excluding the ground cable and including the neutral wire) (1) Screw assembly (2) Spring washer (3) Large washer (optional) (4) Wiring terminals...
Page 167
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-26 Connecting the five-core AC input power cable (including the ground cable and the neutral wire) (1) Screw assembly (2) Spring washer (3) Large washer (optional) (4) Wiring terminals...
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables 6.5 (Optional) Connecting Single-phase AC Input Power Cables NO TE ● This step applies only to some models. The figure is for reference only. ● If a UPS (provided by the customer) or other reliable backup power supplies (provided by the customer) is used to supply power, perform the following steps to change the connection mode of the single-phase AC input power cables.
Page 169
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-27 Wiring diagram (1) Switch 5FCB2, connected to the UPS output ----End Scenario 2: The UPS Obtains Power from the ESS Step 1 Remove the short-circuiting bar from 1–2 and insert it to 2–3 on the XU terminal block.
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-28 Wiring diagram (1) Switch 5FCB2, connected to (2) Binding positions of live (3) Switch 5FCB, connected to the UPS output wire 1775 and neutral wire the UPS input...
Page 171
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-29 Removing the protective cover Step 2 Remove the baffle plates for the signal cables. Figure 6-30 Removing the baffle plates for the signal cables Step 3 Connect the FE communications cables to the WAN ports on the CMU.
Page 172
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-31 Optical cable positions at the bottom (1) DC power cable hole (2) AC input power cable or ground cable hole (3) Optical cable or network cable hole (4) UPS or RS485 cable hole (reserved)
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables ----End 6.6.2 Installing Optical Cables NO TICE Only professionals are allowed to connect optical cables. Figure 6-33 Optical Terminal Box (ATB) interior (1) Fiber spool (2) Cable clip Step 1 Remove the protective cover.
Page 174
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-34 Removing the protective cover Step 2 Remove the baffle plates for the optical cables. Figure 6-35 Removing the baffle plate for the optical cables Step 3 Remove the external mechanical parts from the ATB.
Page 175
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-36 Removing external mechanical parts Step 4 Remove the optical cable fastener. Figure 6-37 Removing a fastener Step 5 Connect one end of the optical jumper to the fiber adapter.
Page 176
LUNA2000-2.0MWH Series Smart String ESS User Manual 6 Installing Cables Figure 6-38 Optical cable positions at the bottom (1) DC power cable hole (2) AC input power cable or ground cable hole (3) Optical cable or FE communications cable (4) UPS or RS485 cable hole (reserved)
LUNA2000-2.0MWH Series Smart String ESS User Manual 7 Checking Before Power-On Checking Before Power-On Item Check Item Acceptance Criteria General Equipment ● The equipment is intact and free from rust or paint inspection appearance flake-off. If paint flakes off, repaint the equipment.
Page 179
LUNA2000-2.0MWH Series Smart String ESS User Manual 7 Checking Before Power-On Item Check Item Acceptance Criteria Accessory The number and positions of external accessories installed meet design requirements. Label All labels are correct, clear, and complete. Cleanness The ESS is clean and tidy inside, without any unnecessary cables, cable ends, terminals, or tools.
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Powering On the System 8.1 Installing the PSU Prerequisites WARNING ● Do not put your hands into the PSU slot to avoid electric shock. ● When the PSU is running, a high temperature is generated around the air outlet at the rear.
Page 181
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Figure 8-1 PSU installation position Procedure Step 1 Push the locking latch leftward. Step 2 Pull out the handle. Step 3 Gently push the PSU into its slot along the guide rails.
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System 8.2 Installing the Solenoid Valve CA UTION ● If a solenoid valve is configured with a reset device, ensure that the solenoid valve is not activated before installing it on the fire cylinder. For details, see ''FAQ''.
Page 183
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Figure 8-3 Installing the Solenoid Valve ----End ● Fire cylinder models: NCM38UFAA, 227M38UFAA, SPS020-MS-032B-EN Step 1 Remove the solenoid valve from the bracket. Step 2 Remove the reset device at the bottom of the solenoid valve.
Page 184
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Figure 8-4 Installing the Solenoid Valve ----End ● Fire cylinder model: P0009438 Step 1 Remove the solenoid valve from the bracket and reinstall the nut and washer. Step 2 Install the solenoid valve on the corresponding stud on the fire cylinder.
Page 186
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Figure 8-7 Power-on process of LUNA2000-2.0MWH-2HX/LUNA2000-2.0MWH- HE2HX NO TICE ● Check the equipment before power-on. For details, see the corresponding user manual. ● Before the first power-on, check that cables are correctly connected.
Page 187
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Procedure Item Remarks Powering On the Smart Array Controller Corresponding (SACU) to number 4 in the power-on flowchart Powering on the Distribution Transformer Corresponding (Huawei or non-Huawei equipment)
User Manual 8 Powering On the System 8.4 Powering On the Smart Transformer Station (STS) ● If a Huawei STS is used, see the corresponding product documents. ● If non-Huawei transformer is used, see the corresponding product documents from the manufacturer.
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System NO TE The digital display meter is started, showing that the line voltage at the low-voltage side is about 400 V, the phase voltage is about 230 V, and the current is 0 A.
Page 190
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Procedure Figure 8-8 Switches in the Control Unit Cabin of LUNA2000-2.0MWH-1HX (1) AC power switch of (2) Extinguishant (3) DC input switch, (4) Battery pack fan the air conditioner...
Page 191
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Figure 8-9 Switches in the Control Unit Cabin of LUNA2000-2.0MWH-1HX (1) AC power (2) Extinguishant (3) PSU AC input (4) Battery pack switch of the air control panel...
Page 192
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Figure 8-10 Positions of the DC circuit breakers of battery racks in the battery cabin (1) Positions of the DC circuit breakers of battery racks in the battery cabin...
Page 193
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Table 8-1 Switch configuration Models Battery Pack Smart Rack Conditioner Conditioner Fans Controller Position in Switches No. Switches No. Switches No. the Battery Cabin LUNA2000-2. 1/2/4/5/7/8/1 3FCB1, 3FCB2, 7FCB7–...
Page 194
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System running well using the battery power supply. Switch on the circuit breaker 5FCB3. Figure 8-11 Position of the power switch in the extinguishant control panel (1) Position of the right power switch in the...
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Models Air Conditioner DC Circuit Breakers No. in Position in the Battery the Control Unit Cabin Cabin LUNA2000-2.0MWH-2 2/4/6/8/10/12 1Q2–3Q2 LUNA2000-2.0MWH-2 1/4/7/10 1Q2–6Q2 LUNA2000-2.0MWH- 1/4/7/10 1Q2–6Q2 HE2HX NO TE The status of DC switches in the control unit cabin is subject to the actual number of PCSs connected.
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System 8.9 Powering On the Smart PCS Precautions NO TICE ● Before turning on the AC switch between the Smart PCS and the power grid, check whether the AC voltage is within the required range using a multimeter.
Page 197
LUNA2000-2.0MWH Series Smart String ESS User Manual 8 Powering On the System Table 8-3 LED indicators Category Indicator Description Status DC indication Steady green The DC side is properly connected, and the voltage on the DC side is greater than or equal to 500 V.
LUNA2000-2.0MWH Series Smart String ESS 9 Deployment and Commissioning (SmartLogger User Manual WebUI) Deployment and Commissioning (SmartLogger WebUI) For details about deployment and commissioning in on-grid scenarios, see Grid Utility-Scale Energy Storage Solution Quick Guide. For details about deployment and commissioning in microgrid scenarios, see...
LUNA2000-2.0MWH Series Smart String ESS User Manual 10 Powering Off the System Powering Off the System 10.1 Delivering a Shutdown Command on the SmartLogger Prerequisites The system has connected to the grid and is running properly. Procedure Step 1 Log in to the SmartLogger WebUI, choose Maintenance > Connect Device, and click to shut down the Smart PCS and Smart Rack Controller.
LUNA2000-2.0MWH Series Smart String ESS User Manual 10 Powering Off the System NO TE Before powering off the system, shut down the entire system on the SmartLogger WebUI, including the Smart PCS and the Smart Rack Controller. Proced Item Remarks...
LUNA2000-2.0MWH Series Smart String ESS User Manual 10 Powering Off the System 10.4 (Optional) Powering Off the Battery Side of the DC LV Panel Step 1 Turn off the switches on the battery side of the DC LV Panel. ----End 10.5 Powering Off the ESS...
Page 203
LUNA2000-2.0MWH Series Smart String ESS User Manual 10 Powering Off the System Model Battery Pack Smart Rack Conditi Conditioner Fan Switch Controller Circuit oner Switch No. Switch No. Break Positio er No. n in in the Contr Battery Cabin Unit...
LUNA2000-2.0MWH Series Smart String ESS User Manual 10 Powering Off the System Step 7 (Optional) Turn off the UPS cable inlet switch 5FCB (as shown by 8 in the switch position diagram). ----End 10.6 Powering Off the Distribution Transformer CA UTION Follow the relevant power operation procedure.
LUNA2000-2.0MWH Series Smart String ESS User Manual 12 Emergency Handling Emergency Handling If an accident (including but not limited to the following) occurs on the site, ensure the safety of onsite personnel first and contact the Company's service engineers. Battery Falling or Strong Impact ●...
Page 207
LUNA2000-2.0MWH Series Smart String ESS User Manual 12 Emergency Handling ● Do not open the door. ● Stay away immediately. ● Cut off the power supply remotely only when your safety is guaranteed. Gas Exhaust ● Onsite personal protection: Do not directly face the exhaust vents.
LUNA2000-2.0MWH Series Smart String ESS User Manual 13 FAQ 13.1 (Optional) How to Level the ESS When Doors Cannot Be Opened or Closed NO TE This procedure applies only to some models. Step 1 Use a jack to support the ESS.
LUNA2000-2.0MWH Series Smart String ESS User Manual 13 FAQ Figure 13-1 The Upper Part of the Lock Tongue Interferes With the Upper Surface of the Lock Base (1) Position of leveling washers Scenario 2: The Lower Part of the Lock Tongue Interferes With the Lower Surface of the Lock Base Use leveling washers to raise ESS by 5–10 mm on the foundation under the lock...
LUNA2000-2.0MWH Series Smart String ESS User Manual 13 FAQ Insert the reset device into the solenoid valve to reset the ejector pin. After resetting, remove the solenoid valve reset device. ----End 13.3 How to Connect the ESS to the Smart PV...
LUNA2000-2.0MWH Series Smart String ESS User Manual 13 FAQ Step 3 Perform the next step as prompted. ----End 13.5 Why Does the PSU Not Start After the Water and Fire Alarms Are Cleared Step 1 Choose Monitoring > Running Param > Fire suppression > Starting up on the SmartLogger WebUI.
LUNA2000-2.0MWH Series Smart String ESS User Manual 13 FAQ 13.6 What Should I Do If the ESU Cable Connection Detection Abnormal Alarm Is Generated on the WebUI? Step 1 Press the reset button ( ) in the upper right corner of the ESU screen. The ESU restarts cable connection detection.
Page 213
LUNA2000-2.0MWH Series Smart String ESS User Manual 13 FAQ Figure 13-5 2U subrack positions Test Instrument Withstand voltage tester Test Items and Criteria Test Item Procedure Criteria Withstand 1. Short-circuit L1, L2, L3, and ● The leakage current voltage of...
Page 214
LUNA2000-2.0MWH Series Smart String ESS User Manual 13 FAQ Test Item Procedure Criteria Main ground 1. Short-circuit L1, L2, L3, and ● The test voltage is 1 insulation resistance 2. Select the insulation ● The stable insulation after L1, L2,...
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Operations on the CMU WebUI A.1 CMU WebUI Operations A.1.1 WebUI Layout Figure A-1 WebUI layout Function Description First-level menu Choose the corresponding first-level menu before you perform any operation over the WebUI.
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Function Description Display language Selects the display language or chooses to log out. Alarm icon Displays the severities and number of active system alarms. You can click a number to access the alarm page.
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Icon Description Icon Description The CMU is in Ascending order or Initializing, Power- descending order icon. off, Idle or other state Click the icon to sort in which the device is...
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Main Menu Second-Level Menu Third-Level Function Menu RS485 Sets RS485 parameters. Modbus TCP Sets Modbus TCP parameters. Other parameters Maintenance Software Upgrade Upgrades the CMU software. Product Information Queries product information.
Page 223
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Procedure Step 1 Connect the network cable between the network port of the PC and the WAN or LAN port of the CMU. Step 2 Set the IP address for the PC on the same network segment as the CMU IP address.
Page 224
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Figure A-2 LAN settings Click OK. Step 4 Log in to the CMU WebUI. In the address box of a browser, enter https://XX.XX.XX.XX (XX.XX.XX.XX is the IP address of the CMU) and press Enter. The login page is displayed. If you log in to the WebUI for the first time, a security risk warning is displayed.
Page 225
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Figure A-4 Login page (Initial login when the user name is displayed as admin) NO TE In this scenario, you need to update the software version to V800R021C10SPC020 or later.
Page 226
– Protect the password by changing it periodically, and keep it secure. If you lose the password, the device must be restored to its factory settings. Huawei will not be held liable for any losses resulting from improper password management.
● If the system displays a message indicating that the loading is successful instead of the upgrade, the delayed upgrade function is triggered. The system automatically performs the upgrade when the conditions are met. ● If the upgrade fails, contact Huawei technical support. A.2.3 Exporting Device Logs Step 1 Access the device log page.
LUNA2000-2.0MWH Series Smart String ESS User Manual A Operations on the CMU WebUI Step 3 Observe the progress bar and wait until the log export is complete. Step 4 After the export is successful, click Log archiving to save the logs.
User Manual B APP Commissioning APP Commissioning B.1 Downloading and Installing the App SUN2000 app: Access Huawei AppGallery and search for SUN2000, or scan the following QR code (or directly visit https://appgallery.cloud.huawei.com/appdl/ C10279542) to download and install the app. QR code: B.2 Logging In to the App...
Page 230
LUNA2000-2.0MWH Series Smart String ESS User Manual B APP Commissioning Procedure Step 1 Press and hold the RST button for 1s to 3s to power on the CMU's built-in WLAN module. NO TE ● If the ALM indicator blinks green fast for 2 minutes and other indicators are off, the WLAN module is powered on.
LUNA2000-2.0MWH Series Smart String ESS User Manual B APP Commissioning Step 3 Select the login user and enter the login password. The main menu screen is displayed. NO TICE ● When you log in to the system for the first time, set the login password. To ensure account security, protect the password by changing it periodically, and keep it secure.
Page 232
LUNA2000-2.0MWH Series Smart String ESS User Manual B APP Commissioning Changing the Login Password of a User After logging in to the app, tap in the upper right corner of the screen, and choose Change password to change the login password.
LUNA2000-2.0MWH Series Smart String ESS User Manual C Crimping an OT or DT Terminal Crimping an OT or DT Terminal Requirements on an OT or DT Terminal ● If a copper cable is used, use copper wiring terminals. ● If a copper-clad aluminum cable is used, use copper wiring terminals.
Page 234
LUNA2000-2.0MWH Series Smart String ESS User Manual C Crimping an OT or DT Terminal Figure C-1 Requirements on an OT or DT terminal Crimping an OT or DT Terminal NO TICE ● Avoid scratching the core wire when stripping a cable.
Page 235
LUNA2000-2.0MWH Series Smart String ESS User Manual C Crimping an OT or DT Terminal Figure C-2 Crimping an OT terminal (1) Cable (2) Core wire (3) Heat shrink tubing (4) OT terminal (5) Hydraulic pliers (6) Heat gun Figure C-3 Crimping a DT terminal...
LUNA2000-2.0MWH Series Smart String ESS User Manual D How Do I Repair Paint Damage? How Do I Repair Paint Damage? Prerequisites ● Do not apply paint in bad weather, such as rain, snow, strong wind, and sandstorm, when there is no shelter outdoors.
Page 237
LUNA2000-2.0MWH Series Smart String ESS User Manual D How Do I Repair Paint Damage? Table D-1 Paint repair description Paint Damage Tool and Procedure Description Material Slight scratch Spray paint or Steps 1, 2, 4, and 1. For the color of...
Page 238
LUNA2000-2.0MWH Series Smart String ESS User Manual D How Do I Repair Paint Damage? Procedure Step 1 Gently polish damaged areas using fine sandpaper to remove smudges or rust. Figure D-1 Polishing a damaged area using sandpaper Step 2 Dip a piece of cotton cloth into anhydrous alcohol and wipe the polished or damaged area to remove the dirt and dust.
Page 239
LUNA2000-2.0MWH Series Smart String ESS User Manual D How Do I Repair Paint Damage? NO TICE ● Ensure that the painting is thin, even, and smooth. ● In the case that an equipment pattern has different colors, to prevent undamaged areas and those with different colors as the damaged area from being contaminated during repainting, cover such areas using white paper and adhesive tape before repairing paint.
Page 240
NO TE The following is a paint model list provided by Huawei. The list may be updated from time to time and is for reference only. The cost of paint and technical services is subject to the local pricing standards.
Preconfigured Huawei-issued certificates are used only in the deployment phase, for establishing initial security channels between devices and the customer's network. Huawei does not promise or guarantee the security of preconfigured certificates. The customer shall bear consequences of all security risks and security incidents arising from using preconfigured Huawei-issued certificates as service certificates.
Page 242
LUNA2000-2.0MWH Series Smart String ESS User Manual E Certificate Management and Maintenance File Path and Name Scenario Replacement /mnt/log/cmu_ca.crt Authenticates the For details about how to validity of the peer SACU replace a certificate, /mnt/log/cmu_client.crt for communication with contact technical support...
LUNA2000-2.0MWH Series Smart String ESS User Manual F Contact Information Contact Information If you have any questions about this product, please contact us. https://digitalpower.huawei.com Path: About Us > Contact Us > Service Hotlines To ensure faster and better services, we kindly request your assistance in providing the following information: ●...
Need help?
Do you have a question about the LUNA2000-2.0MWH Series and is the answer not in the manual?
Questions and answers