Installation and Upgrades for DEFINITY ONE and
IP600 Internet Protocol Release 10 555-233-109
1
Install and Cable the Cabinet
Check AC power and ground for Avaya IP600I
Install coupled bonding conductor
The Coupled Bonding Conductor (CBC) provides mutual inductance coupling
between the CBC and the telephone cables exposed to lightning. The conductor
can be a 10 AWG (#25) (6 mm
cable shield around the exposed cables, or 6 spare pairs from the exposed cable.
For a high-rise building, connect the CBC to an approved building ground on each
floor. To provide the coupled bonding protection:
1. Connect one end of the conductor to a telephone cable building entrance
protector ground that is connected to an approved ground.
2. Route the conductor next to the exposed telephone cables being protected
until it reaches the cross-connect nearest to the telephone system.
3. Position the non-exposed telephone cables at least 12 inches (30.5 cm)
away from exposed telephone cables whenever possible.
4. Terminate the other end to the single-point ground block provided for the
telephone system.
Connect the power cords
!
WARNING:
The AC power cord may connect to a properly rated power distribution unit,
individual AC power receptacles, or to a UPS. A rack-mounted UPS is
recommended.
To connect the power cords:
1. Ensure the circuit breakers at the AC load center are OFF .
2. Connect the cabinet to the UPS or to an "unswitched" or "always on"
electrical outlet.
2
) wire tie wrapped to the exposed cables, a metal
Issue 6
December 2001
1-26