Install and Cable the Cabinet
Check AC power and ground for Avaya IP600I

Connect cabinet grounds and other grounds

Follow these additional grounding requirements:
The approved ground wire must be green, 6 AWG (#40) (16 mm
stranded wire. This is in addition to the ground wire in the AC power cord.
Bond all approved grounds at the single-point ground to form a single
grounding electrode system.
4. Connect the cable as shown in
cabinet, or
Figure Notes
1. 10 AWG (#25) (6 mm
coupled bonding conductor
(CBC).
Figure 1-10. Single-cabinet RMC grounding
Figure 1-10
Figure 1-11 on page 1-25
2
) wire to
for an Avaya IP600 single
for two Avaya IP600 cabinets.
2. 6 AWG (#40) (16 mm
from single-point ground block to the
approved building ground.
Issue 6
December 2001
1-24
2
), copper,
1
2
cadpgnd1 LJK 102500
2
) ground wire