Install and Cable the Cabinet

Check AC power and ground for DEFINITY ONE

Check AC power and ground for
DEFINITY ONE
!
WARNING:
The alternating current (AC) power circuit must be dedicated to the system. The circuit
must not be shared with other equipment and must not be controlled by a wall switch.
The AC receptacle must not be located under the CMC Main Distribution Frame and
must be easily accessible.
!
DANGER:
The latch only removes direct current (DC) power from the cabinet. Unseating the
power supply removes AC power from the power supply, but not from the cabinet. To
remove AC power from the cabinet and pull the AC power cord from the AC appliance
connector on the rear of the cabinet.
!
WARNING:
System grounding must comply with the general rules for grounding provided in Article
250 of the National Electrical Code (NEC), National Fire Protection Agency (NFPA) 70,
or the applicable electric code in the country of installation.
!
WARNING:
AC mains wiring and testing must be performed by a qualified electrician and must
conform to Article 250 of the NEC, NFPA 70, or the applicable electric code in the
country of installation.

Check AC power

Each CMC and RMC uses an auto-ranging (85 to 264 VAC) power supply, 47 to
63 Hz, 330 Watts, 4.5 Amps (100 to120 VAC) or 2.3 Amps (200 to 240 VAC), at
500 VoltAmps (VA).
The AC power source can be 1 phase of 120 VAC with neutral (100 VAC for
Japan) with 15-Amp circuit breaker, or 1 phase of 220 or 240 VAC (200 VAC for
Japan) with 10-Amp circuit breaker. The AC cord uses a NEMA 5-15P plug or an
IEC 320 plug.
Before powering up the system, check the AC power in the equipment room using
a KS-20599 digital voltmeter (DVM) (or equivalent).