Install the DEFINITY ONE system cabinet

Wall-mount the CMC cabinets

!
DANGER:
A fully loaded system with a single CMC cabinet weighs 58 lbs (26.3 kg). Use lifting
precautions. The CMC unit weighs 29 lbs (13.1 kg) with the doors, power unit, and
circuit packs removed.
Install plywood backing on wall
The install technician must provide the plywood and the hardware for mounting.
NOTE:
The following plywood dimensions account for the extra space needed to
install the panels on each side of the cabinet. The cabinet is 24.5 inches
(62.2 cm) wide and each panel is 12 inches (30.5 cm) wide.
Single cabinet installation
1. Install a 3/4-inch (2 cm) thick sheet of 2 x 4-foot (0.6 x 1.2 m) plywood
horizontally onto the wall. See
2. Ensure that the top of the plywood is at least 54 inches (137 cm) from the
floor.
Two vertically mounted cabinets
1. Install a 3/4-inch (2 cm) thick sheet of 4 x 8-foot (1.2 x 2.4 m) plywood
vertically onto the wall. See
Two horizontally mounted cabinets
1. Install 2 3/4-inch (2 cm) thick sheets of 2 x 4-foot (0.6 x 1.2 m) plywood
horizontally onto the wall. See
2. Position the second sheet of plywood to the right of the first sheet, across
from the first cabinet.
Figure 1-26 on page
Figure 1-27 on page
Figure 1-28 on page
Issue 6
December 2001
1-59.
1-60.
1-61.
1-58